E34 Series Installation Guide
Gateway Configuration
(cont.)
Z207251-0C
Page 29 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
value via BACnet, write to the Max_Master property of the device object for the E34E's virtual router.
The next field for the BACnet MS/TP protocol mode is the MSTP_MAC_Addr, which sets the MAC address for the virtual router.
The E34E panel(s) are devices on the internal BACnet network and are not directly addressable as MAC addresses on the MS/TP
network.
The final field for the BACnet MS/TP mode is RTC_Control, which selects which protocol (BACnet or Modbus) has write access to
the RTC. If 0 (BACnet) is selected, the RTC is set using the BACnet Time Synchronization service. If 1 (Modbus) is selected, the RTC
is set by writing to the appropriate Modbus registers.
2. BACnet IP mode
BACnet IP mode uses the same DeviceID_Offset, Virt_Router_Net and RTC_Control parameters described above for BACnet
MS/TP mode. One additional parameter, BACnet_IP_Port, is used to set the UDP port. Most BACnet systems use the default port
(47808 decimal, 0xBAC0 hex) that is recommended in the BACnet standard as the only UDP port. Some large systems need to
segment the enterprise and use more than port. If so, enter the number of the port you need to use to access this device. BACnet IP
mode does not use MSTP_Max_Master or MSTP_MAC_Addr.