Veris Industries E34 Series Installation Manual page 27

Multi-circuit meters
Table of Contents

Advertisement

E34 Series Installation Guide
Gateway Configuration
(cont.)
Z207251-0C
Page 27 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
it is easiest to submit all changes and restart only once when finished with the whole screen. To restart, click the System Restart
button in the row at the bottom of the screen. The restart takes several seconds, during which the server may lose its connection.
Messages appear at the top of the screen indicating current status, but do not perform any actions. Simply allow the tool to
complete the restart cycle.
The first selection in the GUI is Operating_Mode, which has two choices:
1. Locked: used for all normal product operation. It is provided as a tool for high-level technical support. The gateway retains
its current profile configuration when powered.
2. Discovery mode (default): deletes profiles and rediscovers them when the device is powered again. The results are the same,
unless the profile configuration is intentionally altered. Profile selection and discovery are especially important when using
BACnet or SNMP protocols. For normal operation, always use discovery mode.
The second selection in the GUI is Protocol_Mode, used to select the combination of protocols the product communicates
with. The E34E supports five protocols, some of which can operate simultaneously. The table below shows which protocols are
supported in each mode.
Protocol Mode
Primary Protocol
1
BACnet MS/TP
2
BACnet IP
3
SNMP
4
Modbus
To select a primary protocol mode, enter the corresponding number into the text field adjacent to the Primary Protocol option and
click the Submit button to the right of the text field. A prompt appears at the top of the screen instructing the user to restart the
system. When finished, the screen refreshes itself with the appropriate fields for the selected mode.
The next GUI selection, in any protocol mode, is the Upstream_Baud rate selection. If you have selected BACnet MS/TP (mode 1) as
the primary protocol mode, this value sets the MS/TP baud rate. If you have selected modes 2 or 3 as the primary protocol mode,
you may not be using the RS-485 interface at all. If so, this setting can be ignored.
If you have selected BACnet IP, SNMP or Modbus mode, the next selection is Modbus_Address, which sets the Modbus address(es)
for the E34E when access with Modbus RTU with the RS-485 serial connection.
The next selection (in BACnet IP, SNMP or Modbus modes) is Modbus_Parity, which sets the parity of the upstream serial
connection. If using Modbus RTU protocol, set this to match your Modbus master. If not, ignore this field.
The following sections show the field selections (with factory default values) specific to each of the four Protocol_Modes.
©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Ethernet Protocol
RS-485 Protocol
Modbus TCP
BACnet MS/TP
BACnet IP/Modbus TCP
Modbus RTU
SNMP/Modbus TCP
Modbus RTU
Modbus TCP
Modbus RTU