E34 Series Installation Guide
Gateway Configuration
(cont.)
Z207251-0C
Page 23 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
If the E34E IP address parameters are not configured for the network, connect a PC directly and access the GUI from it as follows:
1. Connect a standard Ethernet cable between a PC and the E34E if they are not already connected. Secure a ferrite filter
(included) around the Ethernet cable to ensure the device meets emission requirements.
2. Temporarily change the IP address of the PC to a static value on the same subnet as the E34E. For example: If the E34E is set to
its factory default IP address of 192.168.1.24, set the PC to an unused static IP address on the 192.168.1.xxx subnet (where xxx is
any value between 1 and 255, except 24). Set the subnet mask to 255.255.255.0.
a. Open the Control Panel:
b. In the Control Panel, select Network and Sharing Center. In the Sharing Center, select Change Adapter Settings in the list
at the upper left corner.
c. Select the connection for the network to which the E34E is connected.