E34 Series Installation Guide
Installation (cont.)
Z207251-0C
Page 14 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
8. To connect the stripped CT leads, press the square button on the desired connector input, insert the stripped end of the wire
completely, and release the button.
9. Insert the x1 lead (white wire on Veris CTs) to the inputs on the white connector and the x2 lead (black wire on Veris CTs) to the
inputs on the black connector.
10. Plastic cable ties are included with the product for strain relief on the E34A28 and E34E28. Insert the strain relief device into
one of the available holes on the adapter board (Figure 7A). Gather all current sensor wires connected to that adapter board
and secure the cable tie around them (Figure 7B).
Figure 7
11. The adapter boards are silk screened with labeling for the default configuration of all 3-phase meters. Alternate label overlays
are provided for configurations with all 2-phase meters or all single-phase meters. Channel numbers are provided as well for
setting up and using custom configurations with mixed meter types.
Note: On the E34A28 and E34E28, the adapter board is configured with sequential numbers for the logical meters, but the
channel numbers are in two sets of 42 channels associated with two different Modbus configuration panels (similar register set
at different Modbus addresses).