Before Installation - Takex PR-30BE Instruction Manual

Photoelectric beam sensor
Table of Contents

Advertisement

4

BEFORE INSTALLATION

PROTECTION DISTANCE
Protection distance (between sensor/reflector)
should not exceed the rated range.
Outdoor protection distance may be reduced due to 
the possible effect of mist, fog, frost, rain, or 
condensation on the sensor unit cover and reflector 
unit, which can cause false alarms. 
φA  = 0.2×L 
<Example>
L =  10m (33ʼ )  :  φA = φ2.0m (6.6ʼ)
L = 30m (100ʼ)  :  φA = φ6.0m (20ʼ)
HEIGHT OF INSTALLATION
Install  the  sensor  at  a  height  of  80 to 
100cm(31"to 39") to catch a human 
target. (Install  vertically  so  that  the 
center  of  the  sensor lens and middle 
part of the reflector assembly are 
placed at the same height.)
POSITION OF INSTALLATION
The optical unit can be adjusted horizontally (±90 degrees) and 
vertically (±10 degrees) for various installation types.
(example 1 to 3)
Example 1
INSTALLATION OF MULTIPLE SENSORS
● Multi-level / straight line installation
Do not perform multi-level protection or straight line protection
(3 spans or more), to avoid malfunction or lost alarm.
Straight line protection
(by mounting sensors
  back-to-back)
Straight line protection(3 spans or more)
Center of 
the sensor
80 to 100cm
(31" to 39")
Example 2
Example 3
When BL-11 (optional) is used
Multi-level
protection
In order to use this sensor correctly, thoroughly read this instruction manual and 
select the mounting position and protection distance.
Sensor
OUTDOOR   0.5 to 30m (1.7ʼ to 100 ft.)
INDOOR       0.5 to 40m (1.7ʼ to 135 ft.)
CAUTIONS ON INSTALLATION
Center of 
the reflector 
※Align the center of the sensor with the center
    of the reflector (the middle of the three reflector
    plates) and mount them both keeping the
    protection line horizontal.   When mounting on
    a pole, fix each pole mounting plate at the same 
    height to align the center of the sensor/reflector.
Install the reflector directly, facing the front of the optical unit
as much as possible.
Reflection efficiency of the reflector, due to its nature, decreases
as the angle from the directly facing position increases.
Make sure that angle remains within ±15 ° even if angled
installation is needed. When exceeding this, the amount of
reflected light will be insufficient and it will not operate correctly.
Sensor
MAX15°
In above case, keep the
angle within ±15 °
● Parallel installation
In order to avoid malfunction or lost alarm caused by
interference, keep the distance between each sensor
when installated in parallel as below.
W
L = Within 20m (66ʼ) 
L = Over 20m (66ʼ) but within 30m(100ʼ) 
L = Over 30m(100ʼ ) but within 40m(135ʼ) 
Reflector
Reflector
Right angle 
Correct installation
L
.......................
W = More than 2m (6.6ʼ)
....
W = More than 3m (10ʼ)
  ...
W = More than 4m (13.5ʼ)
φ