Installation - Takex FS-1000E Instruction Manual

Flame sensor

Advertisement

4
WIRING
Wiring is not necessary if power is supplied from battery and external output is not used.
Terminal arrangement
External output
Power output
NPN Open collector output
Action : Detection time +
offdelay 10 sec.
(N.O.)
Capacity : 30V DC 50mA
S
5
4
5 4
3
-
+
S
ALARM
30V DC 50mA
OPEN
COLLECTOR
Make wiring according to
instruction manual.
Single wire (0.14〜1.5mm
can be used for the terminals.
When power cable is wired, remove battery cover to keep
wiring space.
5

INSTALLATION

Locate the installation site.
(Ref : 3, DO'S AND DON'T'S and
7, DETECTION AREA)
Slide the release lever to detach
the sensor unit.
Fix the base with the screws
included.
(Ref : Base installation described
later)
Power input (with polarity)
9 to 30V DC
50mA Max
3
2
ALARM
POWER
S
5 4 3 2 1
2 1
-
+
POWER
9 to 30V DC 50mA
(non-polarity)
DANGER
Don t use the both of external
power supply and battery at 
the same time.
) and twisted wire (0.14〜1.0mm
2
Power supply by battery.
Detach the battery cover from the back side of
(1)
sensor unit with ngers.
(2)
Put Type-AA batteries into battery case with the
correct polarity.
(3)
Plug the connector of battery case into the main
body and con rm the warm-up sound.
(4)
Put wire rst and the battery case next, into the
main body.
(5) Attach the battery cover so that the marks △ on the
cover. Face the marks ▼ on the back of the sensor.
(2)
(4)
(2)
How to use Input / Output
①Power input (terminal (1), (2))
Do not use with battery at same time.
Do not reverse the polarity.
②External output
 The following either (1) or (2) output is available by connecting
open collector output terminal
output terminals.
1. Signal output (terminal (4), (5))
N/O signal is issued for a control panel etc.
When more than 2 sensors are connected on 1 circuit, make
wiring in parallel.
2. Output with voltage (terminal (3), (4))
This output is not available with battery use at the same time.
1
Alarm signal is switched to power input with voltage. (Output
voltage is decreased by approx. 1V compared with input
voltage.) Within the capacity of contact output, alarm devices
(power consumption within 50mA) can be operated by this
output. This is useful for remote control of warning devices etc.
Example of basic connection
 (Remote control by control panel)--- terminal (4), (5)
(1)(2)
Sensor
(3)(4)(5)
S
1
 (Remort control of warning devices) --- terminal (3), (4)
)
2
(1)(2)
Sensor
(3)(4)(5)
S
*Keep the correct polarity
Battery
Battery case - Optional
*Take care not
to catch the
wire between
terminal and
battery.
(5)
(1)
S
and either + or - of extenal
(1)(2)
Sensor
(3)(4)(5)
S
2
Power
The warning devices should be within the capacity
of contact output and adopted for power supply.
Warning devices (buzzer, bell, etc.)
Power supply by wiring
Connect wire to terminals of
(1)
the base.
(Ref : 4, WIRING)
(2)
Detach the battery cover from
the back side of sensor unit
with ngers in order to keep
the wiring space.
To make the exposed wiring,
break the knockout and insert
wires into the wire lead.
knockout
Power
Signal input
(N.O.)
Control panel