Component to be inspected
EPO System Test
Emergency Lighting
Exit signs
Emergency egress
Access control
Component to be inspected
System functional test
—
Third-party components
All maintenance for third-party equipment will be defined by the manufacturer of the equipment. HP will, with
a defined and signed SOW, conduct all maintenance as identified by the original manufacturer.
Examples of external third party components that HP will conduct all manufacturer specified maintenance
with a signed SOW includes:
•
External UPS equipment
Task
EPO NON-FUNCTIONAL TEST
Mode Key Switch Test - rotate
keyed switch through all modes.
ARMED MODE - Verify:
•
Power Indicator - White
•
Armed Light - White
BYPASS MODE - Verify
•
Bypass Light - Green
TEST MODE - Verify:
•
Test Light - Amber
Press EPO button (each in
succession) and thermal trip to
verify:
•
Reset Light - White
•
Audible alarm
•
Visual lamp indicator
Replace light upon failure
Verify emergency lighting is
visible when all lighting is off and
the POD doors are shut.
Visually inspect exit signs for
damage. Replace as necessary.
Personnel door emergency egress
panic bars. (Visual and
operational inspection.)
Task
Visual inspection and operational
test of door access contact
switches
Visual inspection and operational
test of the following:
•
Door access card readers
•
Electric strikes
•
Door release switches at each
personnel door and/or in
each personnel door panic
bar
Frequency
Capable Party
Annually
Qualified personnel
Every 2 years
Qualified personnel
Every 2 years
Qualified personnel
Every 2 years
Qualified personnel
Frequency
Capable Party
Annually
Qualified personnel
Qualified personnel
Annually
Periodic maintenance 68