Epo Thermister; Removing The Epo Thermister; Replacing The Epo Thermister - HP Performance Optimized Datacenter 40c North America Maintenance And Service Manual

Table of Contents

Advertisement

Push the module into the slot on the back of the ECS cabinet door until it clicks into place.
2.

EPO thermister

Two EPO thermisters are located in the hot aisle, both in zone 4.
While the thermisters are not technically at-temperature monitoring devices, when the hot aisle temperature
reaches 60ºC (140ºF), the thermister switch closes. When both thermister switches are closed, the EPO
system initiates an emergency shutdown.
You need scissors for installation.

Removing the EPO thermister

Cut the tie wraps securing the thermister (1).
1.
Pull the thermister down to remove the thermister (2).
2.

Replacing the EPO thermister

Insert the replacement thermister (1).
1.
Removal and replacement procedures 32