Fire Alarm And Suppression System - HP Performance Optimized Datacenter 40c North America Maintenance And Service Manual

Table of Contents

Advertisement

Component to be inspected
Circuit breakers
Sensors
Lighting

Fire alarm and suppression system

Component to be inspected
Full system functional check
Fire panel
VESDA
Task
Panel breaker operational test
(open and shut).
LLS inspection of breakers,
disconnects, motor starters, and
fuse holders (physical).
Breaker fault testing for all
breakers ≥ 250AF
Verify proper operation of:
Internal POD temperature
sensors (thermometer)
Relative humidity sensors (RH
meter)
(Investigate discrepancies, trouble
shoot, and replace as necessary.)
Compare the following with site
indications (if available):
CWS/CWR temperature
CWS/CWR pressure
Flow rate (if possible)
(Investigate discrepancies, trouble
shoot, and replace as necessary.)
POD SHUT DOWN REQUIRED
Calibrate (zero out) POD
differential pressure sensors.
(Investigate discrepancies, trouble
shoot, and replace as necessary.)
Visual inspection of lighting
fixtures and lamps. Replace
components upon failure.
Task
Inspect and perform a functional
check of the system
Inspect and test fire panel
battery backup system
Inspect and test VESDA power
supply
Inspect the VESDA pipe network Every 2 years
Inspect the VESDA filter.
Replace as necessary
Conduct a VESDA pipe integrity
smoke test
Check the VESDA pipe flow
Clean the VESDA sampling
points
Flush the VESDA pipe network
VESDA system air
sampling/smoke test
Frequency
Capable Party
Annually
Licensed electrician
Quarterly
Licensed
electrician/Qualified
personnel
Every 3 years
Third party testing
facility
Annually
Qualified personnel
Annually
Qualified personnel
Annually
Qualified personnel
As needed or
Licensed electrician/
Quarterly
Qualified personnel
Frequency
Capable Party
As required by
Authorized technician
local code
Every 2 years
Authorized technician
Quarterly
Authorized technician
Authorized technician
Annually
Qualified personnel
Annually
Authorized technician
Annually
Authorized technician
Every 2 years
Authorized technician
Every 2 years
Authorized technician
As required by
Authorized technician
local code
Periodic maintenance 66