1

Safety

These operating instructions must always
be available at the place of use of the
device.
1.1

Intended use

The device is for the
• Filtration
of drinking water in domestic water pip-
ing and for residential, commercial and
industrial use. It removes coarse and fine-
grained particles from the drinking water,
which are larger or equal to the mesh size
of the filter, in order to prevent
• pipe damage caused by corrosion
• malfunctions of fittings or control and
regulating devices caused by foreign
bodies.
The filter is suitable for use in cold drinking
water up to a maximum water temperature
of 30 °C (86 °F). The water to be filtered
must comply with the European Drinking
Water Directive.
The device can be installed in all commer-
cially available drinking water pipes. Both
installation and use of the device are sub-
ject to the applicable national regulations.
Particles that are smaller than the
INFO_NO_HEADER
mesh size of the filter supplied and
materials causing cloudiness cannot
be filtered out of the water.
1.2

Application limits

1.2.1 Water quality
The water to be filtered must comply with
the European Drinking Water Directive.
Before using the device with water that
does not comply with this Directive, it is
essential to consult the manufacturer.
4
Safety
1.2.2 Water pressure
CAUTION
The water pressure must not exceed
16 bar input pressure. The device
must not be installed if the mains
pressure is above 16 bar (even for a
short time)!
Nominal pressure
Operating pressure
The water pressure must not fall below
1.5 bar as otherwise backwashing can be
impaired!
Starting at an operating pressure
INFO_NO_HEADER
of 10 bar, increased wear can be
expected!
1.3

Safety instructions

1.3.1 Electrical danger
Risk of electric shock
ELECTRO_NO_HEADER
No electrical wiring or equipment that is
not splash-proof may run or be stored
below the device. Electrical devices/
equipment located in the vicinity of the
device must be splash-proof or comply
with the legal regulations for wet rooms.
1.3.2 Warning of property damage
WARNING
Risk of water damage or damage
to property
The device may only be installed by
qualified technical personnel.
The installation room must be dry and
free from frost.
The ambient temperature must not
exceed 30 °C! In higher temperatures
JUDO JPF+
PN 16
1.5 bar - 16 bar
1701582 • 2018/12