Ratings - ABB DCS880 Quick Manual

Hide thumbs Also See for DCS880:
Table of Contents

Advertisement

10

Ratings

Current and power ratings
See the current ratings including several standard duty cycles for the DCS880 with 50 Hz and 60 Hz supplies
below. The current ratings are based on an ambient temperature of maximum 40°C and an elevation of
maximum 1000 m above mean sea level:
Unit type
I
DC I
continuo
2-Q converters
us
[A]
400 V / 500 V / 525 V
DCS880-S01-0020-04/05**
20
DCS880-S01-0045-04/05**
45
DCS880-S01-0065-04/05**
65
DCS880-S01-0090-04/05**
90
DCS880-S01-0135-04/05
135
DCS880-S01-0180-04/05**
180
DCS880-S01-0225-04/05
225
DCS880-S01-0270-04/05
270
DCS880-S01-0315-04/05**
315
DCS880-S01-0405-04/05**
405
DCS880-S01-0470-04/05
470
DCS880-S01-0610-04/05**
610
DCS880-S01-0740-04/05
740
DCS880-S01-0900-04/05
900
600 V / 690 V
DCS880-S01-0290-06
290
DCS880-S01-0590-06
590
** This unit type can be used as large field exciter. Do not forget the SDCS-DSL-H1x (+S199).
A 10 % current de-rating is strongly recommended.
Notes:
AC current IAC = 0.82 * IDC
Unit type
I
DC I
continuou
4-Q converters
s
[A]
400 V / 525 V
DCS880-S02-0025-04/05**
25
DCS880-S02-0050-04/05**
50
DCS880-S02-0075-04/05**
75
DCS880-S02-0100-04/05**
100
DCS880-S02-0150-04/05
150
DCS880-S02-0200-04/05**
200
DCS880-S02-0250-04/05
250
DCS880-S02-0300-04/05
300
DCS880-S02-0350-04/05**
350
DCS880-S02-0450-04/05**
450
DCS880-S02-0520-04/05
520
DCS880-S02-0680-04/05**
680
DCS880-S02-0820-04/05
820
DCS880-S02-1000-04/05
1000
600 V / 690 V
DCS880-S02-0320-06
320
DCS880-S02-0650-06
650
Ratings
I
I
DC II
DC III
100 %
150 %
100 %
150 %
15 min
60 s
15 min
120 s
[A]
[A]
16
24
16
36
54
35
54
81
52
76
114
74
105
157
100
130
195
125
170
255
165
200
300
195
240
360
235
310
465
300
350
525
340
455
682
435
570
855
540
680
1020
650
240
360
225
470
705
472
I
I
DC II
DC III
100 %
150 %
100 %
150 %
15 min
60 s
15 min
120 s
[A]
[A]
22
33
21
38
57
37
60
90
59
85
127
83
114
171
110
145
217
140
185
277
180
225
337
220
275
412
265
350
525
340
400
600
380
525
787
510
630
945
610
750
1125
725
1087
256
384
246
514
771
508
3ADW000480R0101 DCS880 Quick guide e a
Size
I
DC IV
100 %
200 %
15 min
10 s
[A]
24
15
30
52
31
62
H1
78
49
98
111
73
146
150
93
186
187
110
220
H2
247
148
296
292
180
360
352
215
430
450
270
540
H3
510
310
620
652
425
850
810
525
1050
H4
975
615
1230
337
205
410
H3
708
434
868
H4
Size
I
DC IV
100 %
200 %
15 min
10 s
[A]
31
20
40
55
33
66
H1
88
54
108
124
80
160
165
100
200
210
115
230
H2
270
165
330
330
200
400
397
245
490
510
310
620
H3
570
350
700
765
475
950
915
565
1130
H4
660
1320
369
235
470
H3
762
462
924
H4
Internal
field current
0.3 ... 6 A
1 ... 12 A
1 ... 18 A
2 ... 25 A
2 ... 30 A
-
-
Internal
field current
0.3 ... 6 A
1 ... 12 A
1 ... 18 A
2 ... 25 A
2 ... 30 A
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents