Trane PKG-PRC002-EN Manual page 63

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-47 . SCRF/SIRF 30 Gross Cooling Capacity - 14,000 cfm
75 F
EDB EWB
Tot
Sen
Tot
F
F
MBh
MBh
MBh
70
62
415.4
268.4
401.2
67
453.3
200.0
437.9
62
415.0
333.7
400.9
75
67
452.9
265.1
437.6
72
493.3
196.1
476.6
62
417.7
397.5
404.4
80
67
452.6
330.0
437.2
72
492.9
260.8
476.2
62
435.7
435.8
423.7
85
67
452.7
394.5
437.7
72
492.5
325.2
475.8
Chart PD-61. SCRF/SIRF 30 Fan Performance for CV or with VFD
Chart PD-62. SCRF/SIRF 30 Fan Performance with Inlet Guide Vanes
Air-Cooled
30 Ton
Entering Ambient Air Temperature
85 F
95 F
105 F
Sen
Tot
Sen
Tot
MBh
MBh
MBh
MBh
262.0
386.0
255.3
369.6
193.7
421.4
187.1
403.8
327.3
385.6
320.5
369.3
258.9
421.1
252.2
403.4
190.1
458.7
183.6
439.7
390.3
390.2
382.3
375.4
323.7
420.7
317.0
403.1
254.7
458.4
248.2
439.3
423.7
410.7
410.7
396.7
388.0
421.7
381.1
404.7
319.0
458.0
312.5
438.9
115 F
Sen
Tot
Sen
MBh
MBh
MBh
248.1
352.1
240.5
180.2
384.9
172.8
313.3
352.0
305.6
245.2
384.6
237.8
176.8
419.4
169.7
372.9
360.4
360.8
309.9
384.3
302.4
241.3
419.0
234.1
396.7
381.6
381.6
373.5
386.7
365.2
305.6
418.7
298.3
63

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents