Trane PKG-PRC002-EN Manual page 59

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-43. SCWF/SIWF 80 Gross Cooling Capacity - 29,800 cfm, 240 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
62
891
761
75
67
966
590
72
1049
419
62
910
896
80
67
967
752
72
1048
579
62
961
947
85
67
975
908
72
1047
740
Chart PD-53. SCWF/SIWF 80 Fan Performance for CV or with VFD
Chart PD-54. SCWF/SIWF 80 Fan Performance with Inlet Guide Vanes
Water-Cooled
80 Ton
Entering Water Temp
85 F
Total
Sensible
LWT
MBh
MBh
LWT
83.7
856
746
93.6
84.3
928
575
94.2
85.0
1007
405
94.8
83.8
880
867
93.8
84.3
929
737
94.2
85.0
1006
565
94.8
84.3
930
916
94.2
84.4
938
890
94.3
85.0
1006
725
94.8
95 F
Total
Sensible
MBh
MBh
LWT
819
729
103.4
887
559
104.0
963
389
104.7
847
834
103.7
888
721
104.0
963
550
104.7
896
883
104.1
899
871
104.1
963
710
104.7
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents