Trane PKG-PRC002-EN Manual page 33

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal
cabinet static losses. To determine static pressure to
be used with these curves, add filter, economizer,
flexible horizontal discharge and heat pressure
drops to external duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-4. SCWF/SIWF 20 Gross Cooling Capacity - 8,000 cfm, 60 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
62
244
185
75
67
266
150
72
289
114
62
244
218
80
67
266
183
72
289
147
62
247
246
85
67
265
216
72
288
180
Chart PD-27. SCWF/SIWF 20 Fan Performance for CV or with VFD
Chart PD-28. SCWF/SIWF 20 Fan Performance with Inlet Guide Vanes
Water-Cooled
20 Ton
Entering Water Temp
85 F
Total
Sensible
LWT
MBh
MBh
LWT
84.7
235
181
94.7
85.5
256
146
95.4
86.3
278
110
96.2
84.7
235
214
94.7
85.5
256
179
95.4
86.3
278
143
96.1
84.8
239
239
94.8
85.5
256
211
95.4
86.3
278
176
96.1
95 F
Total
Sensible
MBh
MBh
LWT
225
176
104.6
246
141
105.3
267
106
106.0
226
209
104.6
245
174
105.3
267
139
106.0
231
231
104.8
245
207
105.3
267
171
106.0
33