Trane PKG-PRC002-EN Manual page 47

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-25. SCWF/SIWF 42 Gross Cooling Capacity - 16,800 cfm, 126 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
LWT
62
488
403
84.1
75
67
530
317
84.9
72
576
231
85.6
62
493
473
84.3
80
67
530
397
84.9
72
576
311
85.6
62
513
512
84.6
85
67
532
476
84.9
72
575
391
85.6
Chart PD-41. SCWF/SIWF 42 Fan Performance for CV or with VFD
Chart PD-42. SCWF/SIWF 42 Fan Performance with Inlet Guide Vanes
Water-Cooled
42 Ton
Entering Water Temp
85 F
Total
Sensible
Total
MBh
MBh
LWT
MBh
469
394
94.1
449
510
309
94.7
488
554
223
95.5
531
476
460
94.2
458
510
389
94.7
488
554
303
95.5
530
496
496
94.5
479
512
467
94.8
491
553
383
95.5
530
95 F
Sensible
MBh
LWT
385
104.0
300
104.6
215
105.3
445
104.1
380
104.6
295
105.3
479
104.5
456
104.6
375
105.3
47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents