Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-16. SCWF/SIWF 32 Gross Cooling Capacity - 12,800 cfm, 96 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
LWT
62
367
317
83.9
75
67
398
246
84.6
72
432
175
85.3
62
374
372
84.1
80
67
398
313
84.6
72
431
241
85.3
62
393
393
84.5
85
67
401
377
84.7
72
431
308
85.3
Chart PD-35. SCWF/SIWF 32 Fan Performance for CV or with VFD
Chart PD-36. SCWF/SIWF 32 Fan Performance with Inlet Guide Vanes
Water-Cooled
32 Ton
Entering Water Temp
85 F
Total
Sensible
Total
MBh
MBh
LWT
MBh
352
310
93.8
337
382
240
94.5
365
415
169
95.2
397
361
360
94.0
348
382
307
94.5
365
415
236
95.2
397
380
380
94.4
367
386
370
94.6
369
414
302
95.2
395
95 F
Sensible
MBh
LWT
303
103.7
233
104.3
163
105.0
348
103.9
300
104.3
229
105.0
367
104.3
361
104.4
296
105.0