Trane PKG-PRC002-EN Manual page 39

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-13. SCWF/SIWF 29 Gross Cooling Capacity - 11,600 cfm, 87 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
LWT
62
335
266
84.2
75
67
365
211
84.9
72
397
157
85.6
62
336
315
84.2
80
67
365
262
84.9
72
396
208
85.6
62
347
347
84.4
85
67
365
312
84.9
72
396
258
85.6
Chart PD-33. SCWF/SIWF 29 Fan Performance for CV or with VFD
Chart PD-34. SCWF/SIWF 29 Fan Performance with Inlet Guide Vanes
Water-Cooled
29 Ton
Entering Water Temp
85 F
Total
Sensible
Total
MBh
MBh
LWT
MBh
323
259
94.1
309
352
206
94.8
337
383
152
95.5
366
325
309
94.1
311
352
256
94.8
337
381
202
95.5
366
337
337
94.4
325
351
306
94.8
337
381
253
95.5
366
95 F
Sensible
MBh
LWT
254
104.0
201
104.7
146
105.4
301
104.0
251
104.6
196
105.4
325
104.3
300
104.7
246
105.3
39