Trane PKG-PRC002-EN Manual page 53

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used with
these curves, add filter, economizer, flexible horizontal
discharge and heat pressure drops to external duct static
pressure.
PKG-PRC002-EN
Performance
Data
Table PD-34. SCWF/SIWF 58 Gross Cooling Capacity - 23,200 cfm, 174 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
62
663
571
75
67
720
444
72
782
316
62
675
674
80
67
720
564
72
781
436
62
712
712
85
67
725
679
72
781
555
Chart PD-47. SCWF/SIWF 58 Fan Performance for CV or with VFD
Chart PD-48. SCWF/SIWF 58 Fan Performance with Inlet Guide Vanes
Water-Cooled
58 Ton
Entering Water Temp
85 F
Total
Sensible
LWT
MBh
MBh
LWT
83.9
637
559
93.8
84.6
692
433
94.4
85.3
751
306
95.2
84.1
653
653
94.0
84.6
692
553
94.4
85.3
751
425
95.2
84.5
689
689
94.4
84.6
698
666
94.5
85.3
750
545
95.1
95 F
Total
Sensible
MBh
MBh
LWT
610
547
103.7
662
421
104.3
719
294
105.0
629
629
103.9
662
541
104.3
719
414
105.0
665
665
104.3
669
652
104.4
718
533
105.0
53