1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-19. SCWF/SIWF 35 Gross Cooling Capacity - 14,000 cfm, 105 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
LWT
62
401
320
84.1
75
67
436
254
84.8
72
474
188
85.5
62
402
381
84.1
80
67
436
316
84.8
72
473
250
85.5
62
419
419
84.4
85
67
435
377
84.8
72
473
311
85.5
Chart PD-37. SCWF/SIWF 35 Fan Performance for CV or with VFD
Chart PD-38. SCWF/SIWF 35 Fan Performance with Inlet Guide Vanes
Water-Cooled
35 Ton
Entering Water Temp
85 F
Total
Sensible
Total
MBh
MBh
LWT
MBh
386
313
94.0
369
420
247
94.7
402
456
182
95.4
437
388
373
94.0
373
419
309
94.7
402
455
243
95.4
436
406
406
94.4
392
419
370
94.7
402
455
304
95.4
436
95 F
Sensible
MBh
LWT
306
103.9
240
104.6
175
105.3
365
104.0
302
104.6
236
105.3
392
104.4
363
104.6
297
105.2
43