Trane PKG-PRC002-EN Manual page 55

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-37 . SCWF/SIWF 65 Gross Cooling Capacity - 26,000 cfm, 196 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
62
744
609
75
67
809
480
72
879
351
62
749
726
80
67
809
601
72
878
471
62
780
780
85
67
809
721
72
877
592
Chart PD-49. SCWF/SIWF 65 Fan Performance for CV or with VFD
Chart PD-50. SCWF/SIWF 65 Fan Performance with Inlet Guide Vanes
Water-Cooled
65 Ton
Entering Water Temp
85 F
Total
Sensible
LWT
MBh
MBh
LWT
84.1
715
597
93.9
84.8
779
468
94.6
85.5
845
338
95.4
84.1
722
711
94.0
84.8
778
589
94.6
85.5
844
459
95.4
84.5
756
756
94.4
84.8
779
708
94.6
85.5
844
579
95.4
95 F
Total
Sensible
MBh
MBh
LWT
686
583
103.8
746
455
104.5
810
326
105.2
694
692
104.0
746
576
104.5
810
447
105.2
730
730
104.4
747
695
104.5
808
567
105.2
55