1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
PKG-PRC002-EN
Performance
Data
Table PD-10. SCWF/SIWF 25 Gross Cooling Capacity - 10,000 cfm, 75 gpm
Entering Air
75 F
EDB
EWB
Total
Sensible
F
F
MBh
MBh
LWT
62
281
234
83.9
75
67
306
184
84.5
72
332
133
85.3
62
284
278
83.9
80
67
306
231
84.5
72
332
180
85.3
62
298
298
84.3
85
67
306
278
84.6
72
332
228
85.2
Chart PD-31. SCWF/SIWF 25 Fan Performance for CV or with VFD
Chart PD-32. SCWF/SIWF 25 Fan Performance with Inlet Guide Vanes
Water-Cooled
25 Ton
Entering Water Temp
85 F
Total
Sensible
Total
MBh
MBh
LWT
MBh
270
229
93.8
259
294
179
94.4
281
319
129
95.1
305
274
272
93.8
263
294
227
94.4
281
319
176
95.1
305
288
288
94.3
278
295
272
94.4
283
319
223
95.1
305
95 F
Sensible
MBh
LWT
224
103.6
174
104.3
124
105.0
263
103.8
221
104.3
171
104.9
278
104.2
267
104.3
218
104.9
37