Trane PKG-PRC002-EN Manual page 18

Trane 20-80 ton water-cooled air conditioners 20-60 ton air-cooled air conditioners remote air-cooled condensers manual pkg-prc002-en intellipak signature series
Table of Contents

Advertisement

Table GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80 Tons
Unit Size
42
Compressor Data
Quantity
2/1
NominalTon/Comp
10/15
Circuits
3
Evaporator Coil Data
Rows
3
Sq. Ft.
38.57
Sq. m
(3.58)
FPF
144
Condenser Data
Minium GPM w/o Econ
64
Minium liters / sec. w/o Econ
(4.04)
Minimum GPM w/ Econ
64
Minium liters / sec. w/ Econ
(4.04)
Maximum GPM
142
Maximum liters / sec.
(8.96)
Evaporator Fan Data
Quantity
1
Size (Dia. - inches)
25"
Size (Dia. - mm)
(635)
Minimum HP
7.5
Minimum kW
(5.59)
Maximum HP
30
Maximum kW
(22.37)
Minimum Design CFM
11200
Minimum Design liter / sec.
(5286)
Maximum Design CFM
17850
Maximum Design liter / sec.
(8424)
General Data
EER
14.1
IPLV
13.9
Refrigerant Charge - lbs. R-22
Circuit A
28
Circuit B
24
Circuit C
24
Circuit D
Refrigerant Charge - kg R-22
Circuit A
(12.7)
Circuit B
(10.9)
Circuit C
(10.9)
Circuit D
Capacity Steps - %
100/71/43/26/0
Filter Data
Quantity
4
Size (inches)
16x20x2
Size (mm)
(406 X 508 X 51)
Quantity
8
Size (inches)
16x25x2
Size (mm)
(406 X 635 X 51)
Quantity
2
Size
20x20x2
Size (mm)
(508 X 508 X 51)
Quantity
4
Size
20x25x2
Size (mm)
(508 X 635 X 51)
Notes:
®
1. Compressors are Trane 3D
scroll.
2. EER and IPV are rated in accordance to the ARI Standard 340/360-93. Based on 80/67 F (26.7/19.4 C) to the evaporator coil, nominal airflow and 85-95 F (29.4/35 C) condenser
water.
3. All units operate with R-22. Units ships with full operating charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Filter sizes are for units without hot water or steam heating coils
18
General Data
46
52
2/1
10/15
15
3
4
38.57
49.09
(3.58)
(4.56)
144
144
64
84
(4.04)
(5.3)
64
84
(4.04)
(5.3)
142
186
(8.96)
(11.73)
1
25"
25"
(635)
(635)
7.5
10
(5.59)
(7.46)
30
50
(22.37)
(37.29)
11960
14250
(5645)
(6725)
19550
22100
(9227)
(10430)
14.2
13.1
13.6
12.9
30
28
25
28
25
28
-
-
(13.6)
(12.7)
(11.3)
(12.7)
(11.3)
(12.7)
-
-
100/70/41/30/0
100/65/32/0
4
16x20x2
16x20x2
(406 X 508 X 51)
(406 X 508 X 51)
8
16x25x2
16x25x2
(406 X 635 X 51)
(406 X 635 X 51)
2
20x20x2
20x20x2
(508 X 508 X 51)
(508 X 508 X 51)
4
20x25x2
20x25x2
(508 X 635 X 51)
(508 X 635 X 51)
58
3
3
15
15/10
3
3
2
4
49.09
49.09
(4.56)
(4.56)
144
84
(5.3)
(6.43)
84
(5.3)
(6.43)
186
(11.73)
(14.26)
1
1
25"
27.5"
(635)
(698.5)
10
(7.46)
(7.46)
50
(37.29)
(37.29)
15080
16900
(7117)
(7976)
24650
27625
(11634)
(13038)
13.5
13.1
12.5
12.4
30
30
30
-
-
(13.6)
(12.7)
(13.6)
(12.7)
(13.6)
(12.7)
-
-
(10.9)
100/65/30/0
100/71/44/24/0
4
4
16x20x2
16x20x2
(406 X 508 X 51)
(406 X 508 X 51)
8
8
16x25x2
16x25x2
(406 X 635 X 51)
(406 X 635 X 51)
2
2
20x20x2
20x20x2
(508 X 508 X 51)
(508 X 508 X 51)
4
4
20x25x2
20x25x2
(508 X 635 X 51)
(508 X 635 X 51)
SCWF/SIWF
42-80 Tons
65
72
3/1
3/1
15/10
4
4
3
4
49.09
49.09
(4.56)
(4.56)
144
144
102
102
(6.43)
(7.07)
102
102
(6.43)
(7.07)
226
226
(14.26)
(15.65)
1
1
27.5"
27.5"
(698.5)
(698.5)
10
10
(7.46)
(7.46)
50
50
(37.29)
(37.29)
18700
20800
(8825)
(9817)
29800
29800
(14064)
(14064)
13.0
13.0
11.8
11.4
28
30
28
30
28
30
24
25
(13.6)
(14.5)
(13.6)
(14.5)
(13.6)
(14.5)
(11.3)
(14.5)
100/71/43/23/0
100/73/46/20/0
4
4
16x20x2
16x20x2
(406 X 508 X 51)
(406 X 508 X 51)
8
8
16x25x2
16x25x2
(406 X 635 X 51)
(406 X 635 X 51)
2
2
20x20x2
20x20x2
(508 X 508 X 51)
(508 X 508 X 51)
4
4
20x25x2
20x25x2
(508 X 635 X 51)
(508 X 635 X 51)
PKG-PRC002-EN
80
4
15
4
6
144
112
112
248
1
10
50
32
32
32
32
4
8
2
4

Hide quick links:

Advertisement

Table of Contents
loading