Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
March 2020
( ( 5 5 0 0 H H z z ) )
TTA0604DA/D
TTA0764DA/D
TTA1014DC/D
TTA1264DD
TTA1564DC/D
TTA2014DC/D
TTA2514DC
S S A A F F E E T T Y Y W W A A R R N N I I N N G G
S S S S - - S S V V X X 0 0 0 0 1 1 A A - - E E N N
Split system air conditioner with symbio controls (44 pages)
Summary of Contents for Trane Odyssey TTA0724 A Series
Page 1
Installation, Operation, and Maintenance Split System Air Conditioners Odyssey™ ™ with Symbio™ ™ Controls Cooling Condenser, R-410A 5 to 25 Tons and R-22 Dry Charge 7.5, 10, 15 and 20 Tons ( ( 6 6 0 0 H H z z ) ) ( ( 5 5 0 0 H H z z ) ) TTA0724*A/D TTA0604DA/D...
Page 2
A A L L W W A A Y Y S S r r e e f f e e r r t t o o a a p p p p r r o o p p r r i i a a t t e e S S a a f f e e t t y y D D a a t t a a impact to the environment. Trane advocates the...
Page 3
, , r r e e f f r r i i g g e e r r a a n n t t s s u u b b s s t t i i t t u u t t e e s s , , o o r r r r e e f f r r i i g g e e r r a a n n t t property of Trane, and may not be used or reproduced a a d d d d i i t t i i v v e e s s .
General Information This manual describes proper installation, operation, manual should remain weather-protected with the unit and maintenance procedures for air-cooled systems. until all installation procedures are complete. By carefully reviewing the information within this N N o o t t e e : : It is not the intention of this manual to cover all manual and following the instructions, the risk of possible variations in systems that may occur or improper operation and/or component damage will be...
Pre-Installation Unit Inspection Lifting Recommendations Inspect material carefully for any shipping damage. If W W A A R R N N I I N N G G damaged, it must be reported to, and claims made I I m m p p r r o o p p e e r r U U n n i i t t L L i i f f t t ! ! against the transportation company.
P P r r e e - - I I n n s s t t a a l l l l a a t t i i o o n n “Dimensional Data,” p. 10). Figure 1. Roof mounted unit Outdoor Unit Unit Mounting Gas (Suction)
P P r r e e - - I I n n s s t t a a l l l l a a t t i i o o n n ☐ Insulated portions of liquid line exposed to proper terminals in the unit control enclosure? extremes in temperature? ☐...
Dimensional Data Figure 2. Height, width and depth measurements H - in. (mm) W - in. (mm) D - in. (mm) TTA060, 072, 076, 090 (R-410A) and 39.125 (993.8) 42.125 (1070) 36 (914.4) TTA0902*A (R-22) TTA101, 120 (R-410A) and TTA1202*A (R-22) 39.125 (993.8) 52.125 (1324) 40 (1016)
Page 11
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 3. 5, 6, 6.25, 7.5 ton R-410A and 7.5 R-22 condensing, single compressor (in inches) NOTES: SEE NOTE 3 1.
Page 12
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 4. 5, 6, 6.25, 7.5 ton condensing, dual compressor (in inches) NOTES: SEE NOTE 3 1.
Page 13
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 5. 8.33, 10 ton R-410A and 10 ton R-22 condensing, manifolded compressor (in inches) SEE NOTE 3 NOTES: 1.
Page 14
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 6. 8.33, 10 ton condensing, dual compressor (in inches) SEE NOTE 3 NOTES: 1.
Page 15
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 7. 10.4, 12.5 ton condensing, dual compressor (in inches) SEE NOTE 2 NOTES: 1.
Page 16
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 8. 13, 15, 16.7 and 20 ton R-410A and 15, 20 ton R-22 condensing, dual compressor (in inches) NOTES: 1.
Page 17
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 9. 13, 15, 16.7 and 20 ton condensing, manifolded compressor (in inches) NOTES: 1.
Page 18
D D i i m m e e n n s s i i o o n n a a l l D D a a t t a a Figure 10. 20.9 and 25 ton condensing, manifolded compressor (in inches) SEE NOTE 2 NOTES: 1.
Weights Cooling Condenser Table 1. TTA R-410A unit and corner weights — lbs (60 Hz) Corner Weights Net Max Shipping Tons Model No. Max (lbs) (lbs) TTA0724*A TTA0724*D TTA0904*A TTA0904*D TTA1204*D TTA1204*C 12.5 TTA1504*D TTA1804*D TTA1804*C TTA2404*D TTA2404*C TTA3004*C 1013 Table 2.
Page 20
W W e e i i g g h h t t s s Figure 11. TTA072, 090, 120, 150, TTA060, 076, 101, TTA0902*A, 1202*A Figure 12. TTA180, 240, 300, TTA156, 201, 251, TTA1802*D, 2402*D LIFTING HOLES LIFTING HOLES (BOTH SIDES) (BOTH SIDES) SS-SVX001A-EN...
Installation Refrigerant Piping Guidelines Figure 13. Allowable elevation difference: TTA above indoor unit Contact manufacturer for review Figure 14. Allowable elevation difference: TTA or TWA below indoor unit Contact manufacturer for review Acceptable liquid-riser height based on total liquid-line length (below indoor unit) N N o o t t e e : : Route refrigerant piping for minimum linear length, minimum number of bends and fittings.
I I n n s s t t a a l l l l a a t t i i o o n n Refrigerant Piping Procedures Figure 15. Outdoor units - refrigerant piping (with dry nitrogen) (Outdoor Units) W W A A R R N N I I N N G G R R - - 4 4 1 1 0 0 A A R R e e f f r r i i g g e e r r a a n n t t u u n n d d e e r r H H i i g g h h e e r r P P r r e e s s s s u u r r e e t t h h a a n n R R - - 2 2 2 2 ! ! F F a a i i l l u u r r e e t t o o u u s s e e p p r r o o p p e e r r e e q q u u i i p p m m e e n n t t o o r r c c o o m m p p o o n n e e n n t t s s a a s s...
I I n n s s t t a a l l l l a a t t i i o o n n W W A A R R N N I I N N G G N N O O T T I I C C E E U U n n i i t t D D a a m m a a g g e e ! ! E E x x p p l l o o s s i i o o n n H H a a z z a a r r d d a a n n d d D D e e a a d d l l y y G G a a s s e e s s ! ! D D o o n n o o t t a a p p p p l l y y h h e e a a t t t t o o r r e e m m o o v v e e s s e e a a l l c c a a p p s s u u n n t t i i l l t t h h e e...
N N O O T T I I C C E E TTA0764DA, TTA0904*A, Trane Oil Part Number TTA1014DC, TTA1014DD, E E q q u u i i p p m m e e n n t t D D a a m m a a g g e e ! !
I I n n s s t t a a l l l l a a t t i i o o n n glass when the compressor is running under stabilized N N O O T T I I C C E E conditions and a few minutes after the compressor has E E q q u u i i p p m m e e n n t t D D a a m m a a g g e e ! ! stopped.
I I n n s s t t a a l l l l a a t t i i o o n n Charging Levels Odyssey Application Guide (SS-APG008*- EN) available through e-Library or your I I m m p p o o r r t t a a n n t t : : For the correct line diameter, for line local sales office.
I I n n s s t t a a l l l l a a t t i i o o n n Liquid Charging W W A A R R N N I I N N G G H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e w w / / C C a a p p a a c c i i t t o o r r s s ! ! This procedure is accomplished with the unit operating.
I I n n s s t t a a l l l l a a t t i i o o n n Unit Power Supply Figure 17. Symbio™ ™ jobsite connections Disconnect Switch The installer must provide line voltage circuit(s) to the (By Others) unit main power terminals as shown by the unit wiring See Note 1...
Note: Gray shaded cells indicate older legacy units. Contact the local Trane Commercial Sales office to receive a copy of Hub Case details. 2-Speed Air Handler (identified by a “C” in digit 15) is specifically designed as a replacement air handler for a system with a legacy electromechanical condenser.
Page 30
I I n n s s t t a a l l l l a a t t i i o o n n Pairing A: Symbio Condenser with Constant Volume Air Handler Figure 18. Symbio™ ™ 700 unit controller wiring Symbio 700 Unit Controller 4 10 11...
Page 31
I I n n s s t t a a l l l l a a t t i i o o n n Pairing B: Symbio Condenser with SZVAV / 1. Zone control (see Figure 18, p. 2-Speed Air Handler a.
I I n n s s t t a a l l l l a a t t i i o o n n Refrigerant Circuit Figure 21. Typical split system cooling refrigerant circuit — microchannel COOLING ONLY CIRCUIT DIAGRAM DISCHARGE TEMPERATURE LIMIT (DTL)
Pre-Start Control Circuit Features compressor and the outdoor fans if suction pressure drops below the Low Pressure Cut-Out setting. Once N N o o t t e e : : Not all of these features may be required for your the suction pressure has returned to normal, the unit, check electrical schematic.
Troubleshooting W W A A R R N N I I N N G G Refer to the latest version of the Symbio™ 700 Applications Guide (ACC-APG001*-EN) for details on L L i i v v e e E E l l e e c c t t r r i i c c a a l l C C o o m m p p o o n n e e n n t t s s ! ! troubleshooting the control system.
Service Test Mode The Symbio™ 700 supports a Service Test Mode that energize the appropriate outputs. A user-selected can be used to energize the various components of the timeout value will determine how long the controller system, either to support general system startup tasks will remain in any given state once initiated.
Maintenance W W A A R R N N I I N N G G ☐ Remove any accumulation of dust and/or dirt from the unit casing. H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e w w / / C C a a p p a a c c i i t t o o r r s s ! ! ☐...
Page 37
M M a a i i n n t t e e n n a a n n c c e e The recommended cleaning method for microchannel the pressure washer aimed perpendicular to the face of condenser coils is pressurized water or air with a non- the coil during cleaning.
Wiring Diagram Matrix and Device Location Table 11. TTA wiring diagrams Description Applicability Part Number Power Schematic (Wiring Diagram) for units with Dual All Units with Digit 4-6 = 156/180/201/240 121336380001 Compressors and Dual Fans Power Schematic (Wiring Diagram) for units with Dual All Units with Digit 4-6 = 060/072/076/090/101/ 121336390001 Compressors and Single Fans...
• All accessories for the above products which are fired heat exchanger which has been repaired or sold by Trane and applied in accordance with Trane altered in such manner as, in the judgement of the specifications. warrantor, affects its stability or reliability. This...
Page 44
For more information, please visit trane.com or americanstandardair.com. Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
Need help?
Do you have a question about the Odyssey TTA0724 A Series and is the answer not in the manual?