EN | 17 | ACX120/220 | Commissioning
8.2

Initial verification

Execute the following actions in sequence
by following the display guided procedure
and the illustrations on the screen of the
equipment:
Refrigerant weight check
First tank filling
It is possible to interrupt the initial check
and print a report with the equipment
printer in which the checking status is
reported.
The
equipment
automatic mode until all the steps of the
initial check have been completed.
CAREFULLY ABIDE BY
THE FOLLOWING
INSTRUCTIONS TO
AVOID DANGER TO
PERSONS, THE
DISCHARGE OF
REFRIGERANT IN THE
ATMOSPHERE
Let us consider as first filling the one
carried out during the initial check with
internal tank of the equipment free of
refrigerant and containing air.
Set the quantity of refrigerant to fill (at
least 3 kg) and follow the guided
procedure shown on the display.
Check that the equipment hoses are not
connected and positioned in the hose
winder. Start the procedure that initially
implies the creation of vacuum in the
internal tank. This phase will take 15
minutes and will act on the whole
equipment.
Only when the message appears asking
to connect the charge tank, connect the
HP quick coupler (colour red) of the unit
to an external refrigerant tank using the
supplied adaptor.
© MAHLE
cannot
operate
When the message occurs open the
coupler by turning the knob clockwise.
Open the valve on the external tank.
Just right before reaching the planned
quantity of refrigerant, the unit will stop
and ask the user to close the external
refrigerant tank. Then, the device will
continue the recovery from the hoses and
ends when these are empty. Hence, it is
necessary to open the HP quick-coupler
and disconnect it from the external tank.
Thanks to the E³ CONNECT function, the
refrigerant - usually kept between the
in
cylinder fitting and the hose quick-coupler
until the end of the process - will not be
released in the environment.
There may be two types of source tanks:
with plunger and without plunger.
Tanks with plunger shall remain upright
to be able to transfer liquid refrigerant; for
this type of tanks connect to the L (liquid)
coupler.
Tanks without plunger have only one
valve, so they must be turned upside
down to transfer the liquid refrigerant.
The LP gauge indicates the pressure
inside the external tank.
After
some
automatically end the function.
At the end the weight of the charged
refrigerant will be displayed.
minutes
the
unit
will