Secutron MR-2300 Series Installation And Operation Manual page 59

Lcd fire alarm control panel
Hide thumbs Also See for MR-2300 Series:
Table of Contents

Advertisement

Table 9
Feature Config Menu (Continued)
Feature
Command Menu/MR-2300 Config/Features/
12.Common Supervisory Relay
C o m m o n S u p v . R e l a y
[ X ] E N A B L E
Command Menu/MR-2300 Config/Features/
13.Signal Isolators
S i g - S i l . I s o l a t o r
[ X ] D I S A B L E
Command Menu/MR-2300 Config/Features/
14.Strobe Type
S t r o b e T y p e
[ X ] N O R M A L
Command Menu/MR-2300 Config/Features/
15.Signal Rate (Evacuation Code)
S i g n a l R a t e
[ X ] T E M P O R A L
Command Menu/MR-2300 Config/Features/
16. Active EOL
Active EOL
[X] DISABLE
Default
[X] ENABLE ->Default
[ ] DISABLE
[ ] ENABLE
[X] DISABLE ->Def
[X] NORMAL ->Default
[ ] SECUTRON
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
[X] TEMPORAL->Def
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
[X] DISABLE->Default
[ ] ENABLE
Name in the
Description
Configuration Utility
If enabled, the Common
Supervisory Relay behaves
Supervisory relay
as a common alarm relay. If
used as alarm
disabled, it behaves as a
relay
common supervisory relay
Enable this function only when
Isolators on
suite isolators are used
signal circuits
(Canada only)
Use this menu to select the
manufacturer of the strobes
used in the system. The
selection is system-wide and
applies to all indicating circuits
configured as strobes. For
Strobe
NORMAL strobes there is no
synchronization, while other
strobes are synchronized and
use manufacturer's protocol to
synchronize the strobes.
Use this menu to set the rate
at which the indicating circuits
Signal rate
will sound.
Enable this function if using
an Active EOL. If MR-2300-A
is used, this function should
Active end-of-line
be enabled since the Class A
Converter has built in Active
EOL resistors.
Configuration
59