Technician Settings P189 to P195

P189 – Dehumidification cycle in unoccupied mode
Range: 0...600 minutes
Default: 20 minutes
P190 – Dehumidification break time in unoccupied mode
Range: 0...900 minutes
Default: 40 minutes
P192 – Temperature setpoint for reheat in unoccupied mode
Range: 10...30ºC / 50...86ºF
Default: 15ºC / 59ºF
P194 – Humidity differential band
Range: 0...10 %RH
Default: 5%RH
P195 – Humidity sensor reading offset
Range: -9...+9 %RH
Default: 0 %RH