Wiring and DIP switch configurations 13 to 16 – AC systems
Config. 13:
HC21
Outputs
2/3 Speeds fan
Humidifier, Dehum/
Reheat for Dehumidif
Fan high
11
Fan medium
12
(or Economizer
Fan low
13
Heat element 2
14
(2nd stage heat)
Compressor
15
Heat element 1
16
(1st stage heat)
Humidifier
AO1
Dehumidifier
AO2
(option - See SW2.3)
SW1
SW2
(1)
SW1.1, SW1.2 – Fan speeds:
(2)
SW1.4 – HP (Heat pump):
HC (not heat pump):
(3)
SW1.5 – Compressor delay:
(4)
SW2.3 – Dehumidification:
(5)
SW2.6 – Terminal 12 operation:
See drawing in Wiring terminals and DIP switches (page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
Humidifier, Dehumidifier: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Heat pump, Compressors, Economizer: 110-230 Vac, 0.3A max.
ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
Installation and Operation Guide
Config. 14:
HP21
(1)
2/3 Speeds fan
Humidifier, Dehum/
Reheat for Dehumidif
Fan high
Fan medium
)
(or Economizer
(5)
Fan low
Heat element
(2nd stage heat)
Compressor
(3)
(2)
Heat pump
Humidifier
Dehumidifier
(4)
(option - See SW2.3)
2 speeds (Low and High):
3 speeds (Low, Med., and High):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
ON = Disable, OFF = Enable
ON = Use dehumidifier
OFF = Use reheat for dehumidification
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
Config. 15:
HC22
1 Speed fan, Economizer,
(1)
,
Humid, Dehum/ Reheat
for Dehum
Heat element 2
(2nd stage heat)
Economizer
)
(5)
Fan (1 speed)
Compressor 2
Compressor 1
(3)
Heat element 1
(2)
(1st stage heat)
Humidifier
Dehumidifier
(4)
(option - See SW2.3)
30
Config. 16:
1 Speed fan, Economizer,
Humid, Dehum / Reheat
for Dehum
Heat element
(3rd stage heat)
Economizer
Fan (1 speed)
Compressor 2
(3)
Compressor 1
(3)
(2)
Heat pump
Humidifier
Dehumidifier
(4)
(option - See SW2.3)
SW1.1 = OFF, SW1.2 = ON