Technician Settings P16 to P25

P16 – Enable/Disable Motion sensor
"00" -
Disable
"01" -
Enable
P17 – PIR (Motion sensor) delay time
before switching to unoccupied mode (ON delay)
Range: 0...900 minutes
Default: 20 minutes
P18 – Door switch or key tag configuration
"00" -
Switch On/Off by door switch or key tag
"01" -
Changing the setpoint temperature
"02" -
Switching fan speed to Low
P19 – PIR (Motion sensor) polarity
"00" -
Normally open
"01" -
Normally closed
P25 – Economy setpoint for cooling
Range: 5...35°C / 41...95°F
Default: 30°C / 86°F
ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
Installation and Operation Guide
43
CARRIER CORPORATION ©2020
All rights reserved