Shutdown Procedure - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 15/ 25/ 30/ 33/ 50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

5.18 Shutdown Procedure

When turning off the UPS, the following shutdown procedure should be used:
Move the "STOP/RUN" key switch, located on the front panel, to "STOP." Operation of the
inverter stops. Output power is now provided to the load through the unit's Bypass circuit.
While in this state of operation; if a power failure occurs in the commercial power source, the
UPS will lose power.
charging circuit and chopper circuit remains active.
Do not touch the UPS terminals even though the operation switch has
DANGER
been moved to the STOP position. The UPS may be supplying power
through the Bypass circuit.
The green AC IN lamp is "on" and the green BYP lamp is "on." The LCD screen shows the
following message:
Move the Circuit Breaker to the "off" position. Power is removed from the UPS and to any
attached loads. All lamps are "off" and the LCD screen shows the following message as long
as sufficient power remains to display it:
When the EPO (Emergency Power Off) switch, located on the front panel (or from a remote
located EPO switch) is pushed, the Circuit Breaker is tripped and power is removed from the
UPS and to any attached loads. All LED lamps are "off" and the LCD screen will display the
following message:
TOSHIBA
Power to the critical load device will be interrupted. The battery
BYPASS OPERATION
-
OUTPUT VOLTAGE=207V
>CURRENT 100/100/100%
DATE (DAY) TIME
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
47

Advertisement

Table of Contents
loading

Table of Contents