IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during the installation, maintenance, and
operation of the UPS and its batteries to assure safe and proper operation
1. Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment
or when performing maintenance.
2. Hardwire type UPS units are not equipped with an over-current protection device, nor do they have
an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be provided
between the UPS output and the load input.
3. Battery servicing should be performed by a qualified Toshiba Representative only.
4. Unauthorized personnel should not service batteries.
5. Contact your nearest Toshiba authorized service center for battery replacement.
Qualified Personnel ONLY!
Qualified Personnel is one that has the skills and knowledge relating to the construction, installation,
operation, and maintenance of the electrical equipment and has received safety training on the
hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
1. Have read the entire operation manual.
2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and
equipment, and clear faults in accordance with established safety practices.
3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
4. Be trained in rendering first aid.
5. Be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.
Refer to the Battery System Manual for details on operating and maintaining the battery units for each
system.
UPS System's output is not equipped with an over-current protection device, or an output disconnect for the
AC output; therefore, a circuit breaker should be provided, by the user, between the UPS output and the
critical load input. This device should be rated as follows:
15 kVA
Rated Output
Rating
208/120 VAC
240V, 60A
220/127 VAC
240V, 50A
240
240V, 50A
380/220
480V, 30A
480/277
480V, 25A
600
600V, 20A
TOSHIBA
25 kVA
30 kVA
Rating
Rating
240V, 90A
240V, 110A
240V, 90A
240V, 110A
240V, 80A
240V, 90A
480V, 50A
480V, 60A
480V, 40A
480V, 50V
600V, 35A
600V, 40A
10
33 kVA
50 kVA
Rating
Rating
240V, 120A
240V, 175A
240V, 120A
240V, 175A
240V, 100A
240V, 175A
480V, 70A
480V, 100A
480V, 50A
480V, 80A
600V, 40A
600V, 70A