4200Fa 50Kva W/Internal Transformer - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 15/ 25/ 30/ 33/ 50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

5.6

4200FA 50kVA w/Internal Transformer

Model Number
Rated Output Capacity
External Dimensions
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
Input
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Battery
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Output
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
Efficiency
Heat loss to be removed
Audible Noise
Environment
Operating Temperature
Operating Humidity
Altitude ***
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.
TOSHIBA
Input
# =(B: 208; H: 220; C: 240; N: 380–415; D: 480; M: 600) VAC
Output
*=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye; M:600)
Less than 12 times the rated current under synchronous operation
(Determined by Output Transformer internal to the unit)
± 2% (0–100% balanced load); ± 3% (0–100% unbalanced load)
± 2° (0–100% balanced load); ± 4° (unbalanced load)
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified
technician
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
Automatic Transfer to bypass, then retransfer to inverter
~65dB @ 1 meter from the front of the unit
32°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
35
T42#3*500#AMXN
50 kVA
35.6" X 38.9" X 59.4"
(904mm x 970mm x 1509mm)
208 VAC
+10% to -30%; (-15% to -30%) ****
50 / 60 Hz
3 ∅; 3 Wire + GND
3 ∅; 4 Wire + GND
Greater than 0.98 when in inverter mode
55.0
From 20% to 100% over 5 seconds
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (± 2%)
2% R.M.S.
Refer to Battery System Manual
11.5 Amps
VA / Nominal Output Voltage / 1.73
0.8 lagging
3∅; 4 Wire + GND
± 5V Manually from key pad
50 / 60 Hz
± 0.1% in free running mode
1 Hz/s to 3Hz/s(in 0.5 Hz steps)
125% 90 sec; 150% 30 sec
1000% 10 msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
AC/DC/AC: 88%; DC/AC: 89%
17,743BTU/hr (4,472kcal/hr)
30–90% RH (non condensing)
Less than 2000 meters