Index
Sub-
Name
(Hex)
index
1018
0
Identity Object
1
Vendor ID
2
Product Code
3
Revision Number
4
Serial Number
1200
0
Server SDO
Parameter
1
COB ID Client ->
Server (Rx)
2
COB ID Server ->
Client (Tx)
1400
0
1st Receive PDO
Parameter
1
COB ID Used by PDO
2
Transmission Type
3
Inhibit Time
4
CMS Priority Group
1401
0
2nd Receive PDO
Parameter
1
COB ID Used by PDO
2
Transmission Type
3
Inhibit Time
4
CMS Priority Group
1402
0
3rd Receive PDO
Parameter
1
COB ID Used by PDO
2
Transmission Type
3
Inhibit Time
4
CMS Priority Group
1403
0
4rd Receive PDO
Parameter
1
COB ID Used by PDO
2
Transmission Type
3
Inhibit Time
4
CMS Priority Group
NCAN-02 Installation and Start-up Guide
Attri-
Type
bute
Unsigned8
RO
Number of entries.
Unsigned32
RO
The ABB Vendor ID is 183 (B7h).
Unsigned32
RO
2
Unsigned32
RO
Bits 31-16 correspond to the major revision number and bits 15-0
correspond to the minor revision number.
Unsigned32
RO
Not supported.
Unsigned8
RO
Number of entries.
Unsigned32
RW
Default: 600h + Node ID.
Unsigned32
RW
Default: 580h + Node ID.
Unsigned8
RO
Number of entries.
Unsigned32
RW
Default: 200h + Node ID.
Unsigned8
RW
254 (asynchronous transmission)
Unsigned16
RW
Not supported.
Unsigned8
RW
3
Unsigned8
RO
Number of entries.
Unsigned32
RW
Default: 300h + Node ID.
Unsigned8
RW
254 (asynchronous transmission)
Unsigned16
RW
Not supported.
Unsigned8
RW
3
Unsigned8
RO
Number of entries.
Unsigned32
RW
Default: 400h + Node ID.
Unsigned8
RW
254 (asynchronous transmission)
Unsigned16
RW
Not supported.
Unsigned8
RW
3
Unsigned8
RO
Number of entries.
Unsigned32
RW
Default: 400h + Node ID.
Unsigned8
RW
254 (asynchronous transmission)
Unsigned16
RW
Not supported.
Unsigned8
RW
3
Chapter 6 – Communication
Information
31