RS485 connection to the Dräger REGARD Modbus Card
Dräger RVP 5000
RS 485
(Pin8) TxA
TxB
COMM
TxEN
T x B (PIN1)
RxB
RxA
T x A (Pin2)
TxA
(Pin1) TxB
RJ45
T x B (PIN1)
T x A (Pin2)
O/O G/B B/G Br/Br
ORY 5 4PR/24 A
NOTICE
i
i
Important information for the installed REGARD
system!
Dräger recommends that the Dräger RVP 5000 is only
used in conjunction with a REGARD system consisting
of ATEX channel cards (software revision 3.0). Using a
REGARD 8-channel card software revision 2.5 will
have following effect:
If the 8 channel card is set to latch when full scale
deflection (FSD) is reached this will not be shown on
the RVP 5000 after the input signal falls back into the
normal measuring range. The Dräger RVP 5000 will
show the measuring range instead of the FSD status
that's still displayed on the REGARD system.
26
Dräger Regard Modbus Card
05633194.eps
Setting of the REGARD Modus card
Com-
Com-
Function
mand Na-
mand No.
Software version V 1.9
me
00-0
QUIT
Leave command mode
00-1
P.WD
Enter password
00-2
SAVE
Save settings
00-3
PCHG
Change password
14-0
TLED
Test display and LED's
Test REGARD-
14-6
TSLV
communication
Test Modbus-
14-7
TBUS
communication
52-1
GATE
Set Modbus slave number 1
Function 02 disable
52-2
BAD2
exceptions
Function 04 disable
52-3
BAD4
exceptions
52-4
BAUD
Set baudrate
52-5
PRTY
Set pirarity
REGARD communication
52-6
CKSM
check sum
Set gas concentration
52-7
FRMT
format
60-1
DISP
Switch display on/off
SW2: Set switch on REGARD Modbus card to RS422/485
Default
RVP 5000
Set-
Settings
tings
CCCC
CCCC
1
YES
NO
YES
NO
4800
9600
NONE
NONE
CRC
CRC
SIGN
SIGN
OFF
ON