Machine screw size #10 (or M5 metric) hardware is recommended for mounting
the LCS. Screw shafts of at least 2" (5cm) are recommended. The LCS
mounting holes are 3/8" (9.5mm) in diameter, so ensure that the screw heads
do not exceed this size. Place appropriately sized washers between the screw
heads and the LCS enclosure mounting flanges.
WIRING INSTRUCTIONS
Route the LCS conduit to a nearby service panel or junction box. Use the
included ¼" trade size watertight fitting to provide a moisture-resistant seal wit
the service panel or junction box. If necessary, drill a ½" diameter hole to
accomodate the liquid-tight fitting or use the included ¼" NP to ½" NPT thread
reducer kit.
Figure 6. Wiring the LCS in a
junction box
LCS 230VAC Isolation Monitor User's Manual
Before connecting the LCS
NOTE
service conduc-tors, please
carefully read the section of
this manual titled Service
Connections, on page 9. If you
are unsure of the type of power
provided at the service panel,
please consult with your local
utility or call your Service
Representative for assistance.
NOTE
The three LCS service
conductors use stranded
12AWG, 75ºC copper wire. The
insulation of each conductor is
color coded as follows:
Green:
Black:
White:
Page 9
Protective Earth
Line - 230VAC
Neutral