INSTALLATION

SERVICE CONNECTIONS

CAUTION: To reduce the risk of fire, connect only to a circuit provided
with the appropriate maximum branch circuit overcurrent protection in
accordance with local electrical codes.
For a Model LCS-15, use a 15A circuit breaker.
For a Model LCS-20, use a 20A circuit breaker.
For a Model LCS-25, use a 25A circuit breaker.
For a Model LCS-30, use a 30A circuit breaker.
CAUTION: This is a single-phase device. Do not connect more
than one phase of a 3-phase feed !!! You may use any one phase of a
three-phase wye-connected feed.
CAUTION: The phase used must measure approximately 230V AC to
Neutral. Protective Earth must be connected to Neutral at one or more
points in the system.
CAUTION: Warranty is void if this unit is wired improperly.
WARNING: Only a qualified electrician should perform the installation.
The installation must be performed in accordance with all local electrical
codes and ordinances.
Neutral must be connected to Protective Earth somewhere in the system for any
of the three earthing system arrangements. Ground (earth) fault protection is not
possible unless the Neutral is connected to Protective Earth.
LCS 230VAC Isolation Monitor User's Manual
Page 5