Wire Connection - Optex AX-70TN Installation Instructions Manual

Photoelectric detector
Hide thumbs Also See for AX-70TN:
Table of Contents

Advertisement

4

WIRE CONNECTION

Connect respective wires to the terminals shown in the following figure.
-Terminal
[AX-70/130/200TN]
< Receiver >
Alarm output (N.C.)
Non-voltage contact output
Contact capacity: 28VDC and 0.2A (max.)
Power input
10.5 to 28VDC
[AX-100/200TF]
Alarm output: (N.C./N.O.) switch (In case of using N.O., contact is
not reversed when power supply is off.)
Non-voltage contact output
< Receiver >
Contact capacity: 28VDC and 0.2A (max.)
Power input
10.5 to 28VDC
Use the COM. terminal for both alarm
output and D.Q. circuit.
Environmental Disqualification (N.C.)
Non-Voltage contact output
Contact capacity : 28VDC and 0.2A (max.)
-Wiring distance between power supply and detector
• Ensure that the wiring distance from the power supply is within the range shown in the table on the below.
• When using two or more units on one wire, the maximum length is obtained by dividing the wire length listed
below by the number of units used.
Wire size
12VDC
AWG22
500 m (1700 ft.)
(0.33mm
)
2
AWG20
700 m (2200 ft.)
(0.52mm
)
2
AWG18
1100 m (3600 ft.)
(0.83mm
)
2
AWG16
1700 m (5500 ft.)
(1.31mm
)
2
Tamper output
(It opens when cover is removed)
Non-voltage contact output
Contact capacity: 28VDC and 0.1A (max.)
Tamper output
(It opens when cover is removed)
Non-voltage contact output
Contact capacity: 28VDC and 0.1A (max.)
Power supply voltage
24 VDC
2400 m (7800 ft.)
3500 m(11400 ft.)
5500 m (18000 ft.)
8000 m (26200 ft.)
< Transmitter >
Tamper output : (BE) Model only
(it opens when cover is removed)
Non-voltage contact output
Contact capacity: 28VDC and 0.1A (max.)
Power input
10.5 to 28VDC
< Transmitter >
Tamper output : (BE) Model only
(it opens when cover is removed)
Non-voltage contact output
Contact capacity: 28VDC and 0.1A (max.)
Power input
10.5 to 28VDC
Do not exceed the voltage or current rating
specified for any of the terminals during installation,
doing so might cause fire or damage to the devices.
Note>>
For UL Listed applications, the units shall be connected
to a UL Listed control unit or Listed Burglar Power
Supply capable of providing a minimum of 4 hours
standby power.
EN-6
Note>>
Non-Voltage contact output
Resistive load only
N.C. / N.O. selection Swich
OFF
ON
N.C.
N.O.