Grounding A Media Gateway Powered By Multiple Electrical Panels; Grounding A Media Gateway Expander - Nortel 1000 Installation And Commissioning Manual

Table of Contents

Advertisement

Grounding a Media Gateway powered by
multiple electrical panels

Grounding a Media Gateway Expander

4
Test the ground.
Follow Procedure 6 on
powered by multiple electrical panels.
Procedure 6
Grounding Media Gateways powered by multiple electrical panels
1
Disconnect the AC power cord from the power outlet.
2
Identify the electrical panel powering each component.
3
Install a ground bar for each electrical panel identified above.
Note: Each component must be grounded to the electrical panel that
provides the power to that component.
4
Install a #6 AWG ground wire from the ground lug on the rear of the Media
Gateway to the ground bar identified for that component's power source.
5
Place a DO NOT DISCONNECT tag on the ground wire.
6
Test the ground.
The Media Gateway Expander and the Media Gateway are considered as the
same ground.
Ground the Media Gateway Expander to the Media Gateway.
Communication Server 1000E
Installing system grounds
End of Procedure
page 97
to ground multiple Media Gateway that are
End of Procedure
IMPORTANT!
Page 97 of 466
Installation and Commissioning