GT10/GT30
Transfer Outside
Clock data displayed in the GT10 can be transferred to an external device such as a
PLC, using this setting.
Off - - - The GT10 clock data is not transferred to an external device.
On - - - The GT10 clock data is transferred to an external device.
If "On" is selected for the above "Transfer Outside" parameter, click on the
to specify the output destination and the initial device, and specify the address.
Data storage sequence for internal PLC device
Upper byte
Top address
Minutes data (H00 to H59) Second data (H00 to H59)
Top address +1
Day data (H01 to H31)
Top address +2
Year data (H00 to H99)
Top address +3
* In the day data, H00 indicates Sunday and H06 indicates Saturday.
CAUTION
If "On" is selected for the "Transfer Outside" parameter, the data will be
transferred to the DT90054 as the default device. If this device address
does not exist in the PLC connected to the GT10, however, re - specify
the address so that it matches the model connected to the GT10.
Selecting a device address that does not exist in the PLC will cause an
error (ER61) to occur.
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
Lower byte
Hour data (H00 to H23)
Month data (H01 to H12)
—
Day data (H00 to H06)
GT10 Configuration Settings
button
91