ComAp InteliLite MRS16 Manual page 201

Controller for single gen-set applications
Hide thumbs Also See for InteliLite MRS16:
Table of Contents

Advertisement

Subgroup: Frequency Protection
Generator > Frequency BOC
Setpoint group
Generator settings
Range [units]
Generator > Frequency Wrn (page 201)
Default value
110,0 %
Step
0,1 % of
Comm object
8296
Config level
Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
6 back to List of setpoints
Generator > Frequency Wrn
Setpoint group
Generator settings
Range [units]
Generator < Frequency Wrn (page 202)
Default value
110,0 %
Step
0,1 % of
Comm object
9688
Config level
Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
6 back to List of setpoints
Generator < Frequency BOC
Setpoint group
Generator settings
Range [units]
0,0 ..
Default value
85,0 %
Step
0,1 % of
Comm object
8298
Config level
Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 underfrequency.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
6 back to List of setpoints
InteliLite Global Guide
Related FW
Alternative config
Nominal Frequency (page 159)
Related applications
Related FW
Alternative config
Nominal Frequency (page 159)
Related applications
Related FW
Generator < Frequency Wrn (page 202)
Alternative config
Nominal Frequency (page 159)
Related applications
1.2.1
.. 200,0 [%]
NO
AMF, MRS
1.2.1
..
Generator > Frequency BOC (page 201)
NO
AMF, MRS
1.2.1
[%]
NO
AMF, MRS
[%]
201

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the InteliLite MRS16 and is the answer not in the manual?

Table of Contents

Save PDF