ComAp InteliLite MRS16 Manual page 162

Controller for single gen-set applications
Hide thumbs Also See for InteliLite MRS16:
Table of Contents

Advertisement

Reset To Manual
Setpoint group
Basic settings
Range [units]
Disabled / Enabled [-]
Default value
Disabled
Step
[-]
Comm object
9983
Config level
Advanced
Setpoint visibility Always
Description
If this function is enabled, the controller will switch automatically to MAN mode when there is a red alarm in
the alarm list and fault reset button is pressed. This is a safety function that prevents the gen-set starting
again automatically in specific cases when fault reset button is pressed.
Example: Controller is in AUTO mode and there is red inactive unconfirmed alarm and fault reset
button is pressed, controller will start automatically.
6 back to List of setpoints
Backlight Timeout
Setpoint group
Basic settings
Range [units]
Disabled / 1 .. 255 [min]
Default value
Disabled
Step
1 min
Comm object
10121
Config level
Advanced
Setpoint visibility Always
Description
The display backlight is switched off when this timer exceed. When setpoint is adjusted to disabled then the
display will be backlighted all the time.
6 back to List of setpoints
InteliLite Global Guide
Related FW
Alternative config
Related applications
Related FW
Alternative config
Related applications
1.2.1
NO
AMF, MRS
1.2.1
NO
AMF, MRS
162

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the InteliLite MRS16 and is the answer not in the manual?

Questions and answers

JORGE
March 1, 2025

PARA SABER LA FALLA TIMER ELEPSED

1 comments:
Mr. Anderson
May 14, 2025

The cause of the elapsed timer fault in the ComAp MRS16 is when both Timer1 and Timer2 are active at the same time, but Timer1 has a higher priority. This can lead to a conflict if not configured properly, potentially triggering a fault.

This answer is automatically generated

Table of Contents

Save PDF