Environmental Specifications - VERITAS 5150 Product Description Manual

Hide thumbs Also See for 5150:
Table of Contents

Advertisement

Environmental specifications

Veritas 5150 Appliance technical specifications (continued)
Table A-1
Technical Specification
AC power cable
AC Frequency range
Typical power consumption
Maximum power consumption
System cooling requirement
(heat dissipation)
Operating voltage
Power conversion efficiency
Acoustic noise
See
"Environmental specifications"
The following table lists the environmental specifications for the Veritas 5150
Appliance.
Veritas 5150 Appliance environmental specifications
Table A-2
Specification
Operating temperature
Technical specifications and compliance standards
Veritas 5150 Appliance
Specification: IEC-60320-C14 to IEC-60320-C13, 10A/250V,
Black, 4 ft
The IEC-60320-C14 plugs into a Power Distribution Unit.
The IEC-60320-C13 plugs into an appliance power supply.
Note:
If your power distribution unit is not compatible with
the IEC-60320-C14 plug, then Veritas recommends that
you purchase your power cable locally. Make sure the
power cable meets or exceed the indicated power rating.
See
"Power cables"
50/60Hz
180 watts
400 watts
180 watts (typical) - 614 BTU/hr
400 watts (maximum) - 1365 BTU/hr
100 - 127 VAC
200 - 240 VAC
90% +
70 dBA
on page 30.
Veritas 5150 Appliance
ASHRAE A2 - from 10°C to 35°C with the maximum rate of
change not to exceed 10°C per hour
ASHRAE A3 - up to 40°C for up to 900 hours per year
ASHRAE A4 - up to 45°C for 90 hours per year
Environmental specifications
on page 23.
30