Connection to the flue pipe

The flue pipe must have internal dimensions not larger
than 20x20 cm, or diameter 20 cm. In the event of larger
dimensions, or of the flue pipe being in poor condition ( for
example cracks, poor insulation, etc.), it is advisable to fit
a stainless steel pipe of suitable diameter inside the flue
pipe throughout its length, right up to the top.
Check with suitable instruments that there is a draught
between 3 Pa and 10 Pa (Insert 17), 12 Pa (Insert 25). This
type of connection ensures the evacuation of the fumes
even in the event of a temporary power cut.
At the bottom of the flue pipe, provide an inspection cap
to allow periodic checking and cleaning, which must be
done annually. Make a gas-tight connection to the flue
pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted
which complies with the standards in force
Connection to an external flue with insulated or
double-wall pipe
The only type of pipe which is permissible is insulated
(double-walled) stainless steel, smooth on the inside,
fixed to the wall. Flexible stainless steel pipe must not be
used. At the bottom of the flue pipe, provide an inspection
cap to allow periodic checking and cleaning, which must
be done annually. Make a gas-tight connection to the flue
pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted
which complies with the standards in force.
Check with suitable instruments that there is a draught
between 3 Pa and 10 Pa (Insert 17), 12 Pa (Insert 25).
Connection to the flue pipe
For proper functioning, the connecting pipe between the
Hydro Insert and the chimney or flue duct must have a
slope of not less than 3% in the horizontal stretches, the
length of which must not exceed 2 metres and the vertical
distance between one tee connector and another (change
of direction) must not be less than 1,5 m.
Check with suitable instruments that there is a draught
between 3 Pa and 10 Pa (Insert 17), 12 Pa (Insert 25).
At the botton of the flue pipe, provide an inspection cap
to allow periodic checking and cleaning, which must be
done annually.
Make a gas-tight connection to the flue
pipe, using pipes and connectors as recommended by us.
You must ensure that a windproof cowl should be fitted
which complies with the standards in force.
Fig. 2: connection to the
flue pipe.
Fig.
3:
connection
to
external flue with insulated or
double-wall pipe.