Preparing Your Uninterruptible Power Supply Environment - IBM TotalStorage Installation Manual

San volume controller
Table of Contents

Advertisement

Preparing your uninterruptible power supply environment

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Air temperature
Relative
humidity
48
Installation Guide
Related topics:
v "Preparing your uninterruptible power supply environment"
This topic provides information you need to ensure that your physical site meets
the installation requirements for the uninterruptible power supply.
Attention: Ensure that you comply with the following requirements for
uninterruptible power supplies:
v Each uninterruptible power supply should be connected to a separate branch
circuit.
v A UL listed 15 A circuit breaker must be installed in each branch circuit that
supplies power to the uninterruptible power supply.
v If a rack power distribution unit is used, each uninterruptible power supply
must be connected to a separate power distribution unit.
v The voltage supplied to the uninterruptible power supply must be 200–240 V
single phase.
v The frequency supplied must be between 50 and 60 Hz.
Note: If the uninterruptible power supply is cascaded from another
uninterruptible power supply, the source uninterruptible power supply must
have at least 3 times the capacity per phase and the total harmonic
distortion must be less than 5% with any single harmonic being less than
1%. The uninterruptible power supply must also have input voltage capture
that has a slew rate faster than 3 Hz per second and 1 msec glitch rejection.
Dimensions and weight:
Height
Width
89 mm
483 mm
(3.5 in.)
(19 in.)
AC input-voltage requirements:
Power supply assembly
type
220 V
Environment:
Operating
Nonoperating
environment
environment
0°C to 40°C
0°C to 40°C
(32°F to 104°F)
(32°F to 104°F)
5% to 95%
5% to 95%
noncondensing
noncondensing
Altitude:
Depth
622 mm
(24.5 in.)
Voltage
160 to 288 V ac
Storing
environment
0°C to 25°C
(32°F to 77°F)
5% to 95%
noncondensing
Maximum
weight
39 kg
(86 lb.)
Frequency
46 to 64 Hz
Shipping
environment
–25°C to 55°C
(–13°F to 131°F)
5% to 95%
noncondensing

Advertisement