Vitocom 300 (type FA3, FE1 and FI1),
H Type FA3
part no. 7143 428
H Type FE1
part no. 7143 430
H Type FI1
part no. 7143 429
In conjunction with the Vitodata 300:
H For remote notification, remote
monitoring and scanning of faults
and/or data points via the internet
H Remote switching, remote setting of
parameters and codes for heating
systems via the internet
Configuration via:
H Vitosoft 200, type LNR via Optolink
H Vitodata 300
Data points provided by the heating
control unit are hooked up to the
Vitocom 300 via LON. Additional settings
can be made during commissioning, if
system-specific special functions, such as
monitoring limits, are required.
Fault messages are reported to the
Vitodata 300 server via the internet.
These messages are then transferred by
the Vitodata 300 server to the following
communication services:
H PC with internet access
H Fax
H SMS to D1/D2/E Plus/O
mobile phones
2
H E Mail
H Voicemail
Standard delivery:
H LON cable RJ45 RJ45 for data
exchange between the Vitotronic and
the Vitocom 300 (7.0 m long)
*1
H Power supply unit
H Mains connecting cable from the power
supply unit to the base module
*1
H Base module
(with 8 digital inputs, 2
digital outputs and 2 sensor inputs):
Type FA1: with integral analog
modem and connecting cable for
telephone socket TAE 6N (2.0 m long)
Type FE1: with connecting cable with
RJ45 plug and sub D plug (9 PIN) as
modem connecting cable (GSM
modem accessories) or suitable
external ISDN terminal adaptor
Type FI1: with integral ISDN modem
and connecting cable with RJ45 plug
for ISDN socket (2.0 m long)
*1
Rail mounting TS35 to DIN EN 50 022, 35 × 15 and 35 × 7.5.
VITODENS
Vitotronic 200 and Vitotronic 333 accessories
Accessories:
*1
H Expansion module
part no. 7143 431:
10 digital inputs
7 analog inputs (2 may be configured
as pulsed inputs)
2 digital outputs
See the base module for dimensions
*1
H Expansion module
part no. 7159 767:
10 digital inputs
7 analog inputs (2 may be configured
as pulsed inputs)
2 digital outputs
1 M BUS master for the connection
of, for example, up to 250 M BUS
capable heat meters with M BUS
slave interface to EN 1434 3
See the base module for dimensions
H Wall mounting enclosure for the
installation of the Vitocom 300 module,
if no control panel or electrical
distribution panel is available
2 tier
part no. 7143 434
3 tier
part no. 7143 435
H Uninterruptible power supply unit
(UPS)
part no. 7143 432
H Additional rechargeable battery pack
for UPS
part no. 7143 436:
possible for: 1 base module,
1 expansion module and allocations
for all inputs
required for: 1 base module and
2 expansion modules
H Extension of the connection cable:
Installation distance between
7 and 14 m:
1 connecting cable (7.0 m long)
part no. 7143495
1 LON coupling RJ45
part no. 7143 496
Installation distance between
14 and 900 m:
2 connecting cables (7.0 m long)
part no. 7143 495
2 core cable, CAT5, screened or
JY (St) Y 2 × 2 × 0.8
on-site
2 LON socket RJ45, CAT 6
part no. 7171 784
On-site requirements:
H Analog telephone connection
For type FA3 with TAE socket,
code "6N"
For type FI1 with RJ45 socket (ISDN)
H LON communication module
(accessories)
1.2 Specification
Power supply unit (standard delivery
Vitocom 300):
Specification
Rated voltage:
85 to 264 V~
Rated frequency:
50/60 Hz
Rated current:
0.55 A
Output voltage:
24 V
Output current:
1.5 A
Safety class:
II
Protection:
IP 20 to EN 60529;
safeguard through
design/installation
Primary/secondary
earth separation:
SELV to EN 60 950
Electrical safety:
EN 60 335
Permissible ambient
*1
temperature
in operation with
input voltage
20 ºC to +55 ºC
*1
,
U
187 V to 264 V: Installation in living
E
space and boiler
rooms (standard
ambient conditions)
in operation with
input voltage
5 ºC to +55 ºC
U
100 V to 264 V: Installation in living
E
space and boiler
rooms (standard
ambient conditions)
during storage
and transport:
25 ºC to +85 ºC
1
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 300Vitodens 333Vitodens 343