Viessmann Vitodens 200 Technical Manual page 22

4.2 kw to 66.0 kw
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

1.2 Specification
Vitotronic 100, type HC1, for constant temperature mode
Vitotronic 100, type HC1, for constant temperature mode
Structure and functions
Modular construction
The control unit comprises a basic unit,
electronic modules and a programming
unit.
Integrated into the Vitodens.
Basic unit:
1
H ON/OFF switch
H Optolink laptop interface
H Operating and fault indicator
H Reset button
Programming unit:
H Display
H Adjustment and display of
temperatures and codes
H Fault message display
H Keys:
Program selection
Boiler water temperature
DHW temperature
DHW convenience function
Emissions test function
Functions
H Electronic boiler control unit for
operating at a constant boiler water
temperature
H A Vitotrol 100, type UTA or UTD is
required for room temperature-
dependent operation (according
to EnEV [Germany])
H Heating system frost protection
H Integrated diagnostic system
H Integral cylinder thermostat
Control characteristics
PI characteristics with modulating output.
Specification
Rated voltage:
230 V~
Rated frequency:
50 Hz
Rated current:
6 A
Safety class:
I
Protection:
IP X4 D to EN 60529,
safeguard through
design/installation
Function:
Type 1 B to EN 60730 1
Permissible ambient
temperature
H in operation:
0 ºC to +40 ºC
Use in living space
and boiler rooms
(standard ambient
conditions)
H during storage
and transport:
20 ºC to +65 ºC
Electronic control
thermostat setting: 74 ºC (change
not possible)
22
Electronic
temperature
limiter setting:
(heating operation): 81 ºC (a changeover
not possible)
Temperature
limiter
setting:
100 ºC (change
not possible)
Setting range for
the DHW
temperature
H Gas fired
H
combi boilers:
10 ºC to 57 ºC
H Gas fired boilers, Vitodens 333 and
H
Vitodens 343:
10 ºC to 63 ºC
Setting heating programs
The heating system frost protection (see
frost protection function) applies to all
heating programs. You can set the
following heating programs with the
program selection keys:
H Heating and DHW
H DHW only
H Standby mode
Frost protection
The frost protection function is active in
all heating programs.
The burner is switched ON when the
boiler water temperature reaches 5 ºC and
will be switched OFF again, when the
boiler water temperature reaches 20 ºC.
The circulation pump will be switched ON
simultaneously with the burner and
switched OFF after a delay.
The DHW cylinder is heated to
approx. 20 ºC.
To protect the system from frost, the
circulation pump may be started at
certain intervals (up to 24 times per day)
for periods of approx. 10 minutes.
Summer mode
Heating program "w"
The burner starts only when the cylinder
needs reheating or when DHW is drawn
from a combi boiler.
Boiler water temperature sensor
The boiler water temperature sensor is
connected to the control unit and built
into the boiler.
Permissible ambient
temperature
H in operation:
20 ºC to +130 ºC
H during storage
and transport:
20 ºC to +170 ºC
Cylinder temperature sensor
Standard delivery for
H Connection set for wall mounted DHW
cylinders (80 litres) (order separately)
H Connection set for DHW cylinders
mounted below the boiler (120 litres or
150 litres) (order separately)
H Connection set for DHW cylinders
installed adjacent to the boiler
(160, 200 or 300 litres) or alternative
DHW cylinders (order separately)
H Order the cylinder temperature sensor
for the Vitodens 300 from 49 kW output
separately (see page 23).
Cable length approx. 3.75 m, wired ready
to plug in
Protection:
IP 32
Permissible ambient
temperature
H for operation:
20 ºC to +90 ºC
H during storage
and transport:
20 ºC to +70 ºC
Cylinder temperature sensor
(Vitodens 333 and 343) and primary
temperature sensor
(only for the Vitodens 333)
The sensors are connected to the control
unit and built into the boiler.
Protection:
IP 32
Permissible ambient
temperature
H for operation:
20 ºC to +90 ºC
H during storage
H
and transport:
20 ºC to +70 ºC
VITODENS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 300Vitodens 333Vitodens 343

Table of Contents