5.1 Regulations and Directives
5.1 Regulations and Directives
The design and operational
characteristics of the Vitodens gas fired
condensing boilers from Viessmann meet
the requirements of EN 297.
They are CE-designated.
They may be installed in sealed heating
systems with permissible flow
temperatures (= safety temperatures) up
to 100 ºC to EN 12828. The maximum
flow temperature is approx. 15 K below
the safety temperature.
Observe all standards and guidelines
applicable to the installation and
operation of this system in your country.
EnEV
Energy Savings Order
st
1
BImSchV
First order for the implementation of the Federal Immission Protection Act
(Order for small and medium combustion systems)
FeuVo
Federal Combustion Order
DIN 1986
Drainage system materials
DIN 1988
Drinking water pipe systems on property
DIN 4701
Rules for calculating the heat demand of buildings
DIN 4753
Boilers and boiler systems for DHW and operating water
DIN 18 160
Domestic chimneys
5
DIN 18 380
Central heating systems and central DHW heating systems (VOB)
DIN 57 116
Electrical equipment for combustion systems
EN 677
Gas fired condensing boilers
EN 12828
Heating system in buildings Designing hot water heating systems
EN 13384
Flue gas systems Thermal and flow calculations
ATV DVWK A 251 Introducing condensate from gas and oil fired combustion systems into public sewers
DVGW G 260
Gas quality
DVGW G 600
Technical rules for gas installations (TRGI)
DVGW G 688
Gas-consuming equipment, condensing technology
DVGW/DVFG
Technical rules for Liquid Petroleum Gas (TRF)
DVGW VP 113
Systems comprising gas fired combustion equipment and flue pipes
VDI 2035
Guidelines for the prevention of damage through corrosion and scaling in hot water heating systems
VdTÜV 1466
Water Quality Code of Practice
VDE Regulations and special regulations of public utilities.
178
Only qualified personnel should carry out
the installation, the mains gas and flue
gas connections, the commissioning, the
electrical wiring as well as maintenance
and repair work.
The installation of a condensing boiler
may need to be notified to and approved
by your local gas supplier.
Some regional permits may be required
for the flue gas system and the
condensate drain into the public sewer.
Some countries require the notification of
the flue gas inspector and the water
authorities before installation
commences.
We recommend that you carry out
maintenance and cleaning procedures
annually. As part of this maintenance
procedure, check the correct function of
the entire system. Remedy all faults.
Condensing boilers must only be
operated with specially designed, tested
and approved flue pipes.
Only recognised contractors may convert
this boiler for use in countries other than
those stated on the type plate. That
contractor must also arrange the
acceptance in accordance with the
statutes of that country.