4.2 Design and sizing information for connection on the flue gas side
Installation and dimensions
3
b1
4
Flue pipe
Flue pipe
a
∅ mm
∅ mm
min. mm
max. mm
125
700
1 000
150
700
1 000
Install the flue gas header with a slope of
at least 3º.
Given a clearance of 100 mm respectively
between the boilers, the unions between
the boiler and the non-return valve
should be trimmed in accordance with
the dimensions b1 to b4 shown in the
table.
VITODENS
2
1
a
b3
b2
min. 100
max. 400
b1
b2
min. mm
min. mm
239
276
239
276
The unions between the boilers can be
matched up on site.
d
b4
(max.)
5
1 Flue gas header ∅ 125 or 150 mm
2 Non-return valve ∅ 100 mm
3 Terminal piece with condensate drain
4 Siphon with hose
5 Inspection piece ∅ 125, 150 or 200 mm
6 Ventilation bezel
b3
b4
c
min. mm
max. mm
min. mm
313
350
200
313
350
200
6
d
e
mm
mm
250
220
250
240
163
300
4