3.2 Installation examples
System design 10
300
System design 10
Vitodens 300 (from 49 kW) with/without DHW cylinder with low loss header, one heating circuit without mixer and one heating
circuit with mixer
3/230V
2/K
V
3/230V
U
T
S
3
Required electrical connecting cables
2/K
Number of cores/low voltage
3/230 V Number of cores/230 V~
Required equipment
Item
Description
A
Vitodens 300 (from 49 kW) with control unit for weather-compensated mode
C
Vitotrol 200
or
Vitotrol 300
F
Temperature limiter for limiting the max. temperature of underfloor heating systems
Immersion thermostat
or
Contact thermostat
H
Heating circuit pump (e.g. in Modular Divicon)
K
Heating circuit pump (e.g. in Modular Divicon)
N
Extension kit for one heating circuit with mixer plus flow temperature sensor
O
Flow temperature sensor for low loss header
P
Low loss header
R
Primary pump (boiler circuit), variable speed
S
Cylinder primary pump
T
Cylinder temperature sensor
U
DHW cylinder
V
External extension H 1
100
F
C
G
B
2/K
A
H
2/K
L
2/K
M
N
~
2/K
M
3/230V
2/K
3/230V
R
O
P
Note
For a volume flow of < 0.3 m
3
> 3.5 m
/h, install a low loss header
(see specification).
Please observe the residual head of the
primary pump (see page 86).
E
D
K
3
/h or
A Vitodens 300 (from 49 kW) with
control unit for weather-compensated
mode
B Outside temperature sensor
C Vitotrol
D Underfloor heating circuit
E Radiator heating circuit
F Maximum temperature limiter
G Flow temperature sensor
H Heating circuit pump (heating circuit
with mixer)
K Heating circuit pump (heating circuit
without mixer)
L Regulating valve
M Three-way mixer
N Extension kit for one heating circuit
with mixer
O Flow temperature sensor for low loss
header
P Low loss header
R Boiler circuit pump
S Cylinder primary pump
T Cylinder temperature sensor
U DHW cylinder
V External extension H 1
The radiator heating circuit is supplied by
the on-site circulation pump.
The underfloor heating circuit is supplied
by an on-site circulation pump, which is
controlled by the extension kit.
The DHW circulation pump is connected
on site.
Low loss headers are available in
conjunction with Modular Divicon or
individually as an accessory.
See Vitotec or Vitoset pricelist.
For further details regarding low loss
headers, see page 118.
Quantity Part no.
1
as per pricelist
1
7450 017
1
7179 060
1
7151 728
1
7151 729
1
as per pricelist
1
as per pricelist
1
7178 995
or
7178 996
1
7179 488
1
as per pricelist
1
7178 820
1
7339 468
1
7179 114
1
as per pricelist
1
7179 058
VITODENS