Viessmann Vitodens 200 Technical Manual page 143

4.2 kw to 66.0 kw
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

4.2 Design and sizing information for connection on the flue gas side
Plastic (PPs) balanced flue system for external wall terminal
(type C
, according to TRGI '86/96)
13x
Note
The external flue terminal is only
compatible with existing building
standards, if another flue gas route is
inappropriate on technical or economical
grounds.
According to TRGI '86/96, item 5.6.1.1, the
external wall terminal is only permissible
for boilers with rated output up to 11 kW
(central heating) or 28 kW (DHW heating).
The conversion to 11 kW central heating
should be documented by the heating
engineer carrying out the conversion on
an additional type plate.
It was verified as part of the CE approval
test that nowhere on the Vitodens or the
balanced flue system surface will
temperatures higher than 85 ºC occur.
a
a
a
a
a
a
a
a
a
a
a
a
1
1
1
1
1
1
1
1
1
1
1
1
5
5
5
5
5
5
5
5
5
5
5
5
7 4
7 4
7 4
7 4
7 4
7 4
7 4
7 4
7 4
7 4
7 4
7 4
6
6
6
6
6
6
6
6
6
6
6
6
4
4
4
4
4
4
4
4
4
4
4
4
2
2
2
2
2
2
2
2
2
2
2
2
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
A Ventilation air
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
B Flue gas
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
Balanced flue adaptor for system 80/125 to system 60/100
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
and 70/110
80/125
80/125
80/125
80/125
80/125
80/125
80/125
80/125
80/125
80/125
80/125
80/125
60/100
60/100
60/100
60/100
60/100
60/100
60/100
60/100
60/100
60/100
60/100
60/100
VITODENS
Observe the implementation information
according to TRGI '86/96, item 5.6.4.6 [or
local regulations], in particular the
arrangement/position of the wall outlet.
H Vitodens 300, 13 kW and 343:
Int. dia. flue pipe
∅ 60 mm
Int. dia. ventilation pipe
∅ 100 mm
H Vitodens 200, Vitodens 300, 26 kW to
35 kW and Vitodens 333:
Int. dia. flue pipe
∅ 80 mm
Int. dia. ventilation pipe
∅ 125 mm
Max. number of bends
H 87º:
2 pieces
or
H 45º:
3 pieces
For a different number of elbows, deduct
or add to the given max. extended length
1 m for 87º bends or 0.5 m for 45º bends.
Install an inspection aperture for checking
and cleaning the flue pipe.
Rated output
1 Flue outlet
(part of the standard boiler delivery)
A
A
A
A
A
A
A
A
A
A
A
A
2 Balanced flue wall terminal (incl. wall bezel)
3
3
3
3
3
3
3
3
3
3
3
3
3 Guard grille
B
B
B
B
B
B
B
B
B
B
B
B
required (available upon request), if the
combustion air and flue pipe aperture lie at
a height of up to 2 m above ground level in
areas of public or private traffic.
4 Balanced flue pipe
1 m long
0.5 m long
5 Balanced flue bend
87º (1 piece)
45º (2 pieces)
or
Balanced flue inspection tee piece
87º (1 piece)
6 Balanced flue inspection piece, straight
(1 piece)
7 Balanced flue sliding coupling
Fixing clamp, white (1 piece)
Balanced flue adaptor
H ∅ 80/125 mm to ∅ 60/100 mm
H ∅ 60/100 mm to ∅ 80/125 mm
H ∅ 80/125 mm to ∅ 70/110 mm
H ∅ 70/110 mm to ∅ 80/125 mm
*1
Vitodens 300 and Vitodens 343 with 13 kW.
*2
Vitodens 333 with 13 kW.
The external flue terminal has been tested
and CE-designated as a concentric
balanced flue system as one technical
unit with the Vitodens condensing boiler.
A function verification according to
EN 13384 is not required.
kW
13
System size
∅ mm
60
60
60
60
60
60
60
60
60
60
*1
*2
13
35
80
80
80
4
80
80
80
80
80
80
80
80
80
143