9.2. e lectrical installation with circular
plug-in connector
Connect the positioner according to the table.
5
6
4
7
3
8
2
1
Fig. 8:
Circular plug M12 x 1, 8-pole
pin
Wire color
configuration
3)
1
white
Set-point value
2
brown
Set-point value
3
green
Supply voltage
4
yellow
Supply voltage
5
grey
Binary input
6
pink
Binary input
7
Analogue position feedback
blue
8
Analogue position feedback
red
Tab. 3:
Connection with circular plug-in connector
When the supply voltage is applied, the positioner is operating.
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled "10.2. Automatic adjustment X.TUNE".
The indicated colors refer to the connecting cable available as an
3)
accessory (919061).
16
(0/4 ... 20 mA)
+
GND
GND
24 V DC
+
+
GND
GND
+
english
Type 8696

Start-up

10. sTarT-up
10.1. safety instructions
Warning!
risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/
the device.
10.2. a utomatic adjustment X.TUNE
To adjust the positioner to local conditions, the X.TUNE
function must be run following installation.
Warning!
While the X.TUNE function is running, the valve automatically
moves from its current position!
• Never run X.TUNE while a process is running!
• Take appropriate measures to prevent the equipment from being
accidentally actuated!

Advertisement